7KM2112-0BA00-2AA0 - SENTRON PAC3200; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES VAUX: 110-340VDC / 95-240VAC VIN: MAX.690/400V; 45-65HZ AMPIN: X/1A OR X/5A AC RING LUG TERMINALS (siemens) - Quad Industry GmbH

Артикул: 7KM2112-0BA00-2AA0
Наименование: SENTRON PAC3200; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES VAUX: 110-340VDC / 95-240VAC VIN: MAX.690/400V; 45-65HZ AMPIN: X/1A OR X/5A AC RING LUG TERMINALS (siemens)
Производитель: Siemens


Наименование продукта
SENTRON PAC3200; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES VAUX: 110-340VDC / 95-240VAC VIN: MAX.690/400V; 45-65HZ AMPIN: X/1A OR X/5A AC RING LUG TERMINALS
Жизненный цикл продукта
7KM2112-0BA00-2AA0">
7KM2112-0BA00-2AA0"> Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
7KM2112-0BA00-2AA0"> 2008-04-07
Manuals weitere>>
7KM2112-0BA00-2AA0"> Справочник по аппарату SENTRON Многофункциональное устройство PAC3200  2011-10-18
Similar to image
SENTRON PAC3200; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES VAUX: 110-340VDC / 95-240VAC VIN: MAX.690/400V; 45-65HZ AMPIN: X/1A OR X/5A AC RING LUG TERMINALS
 
General technical data:
product designation   multimeter
product brand name   SENTRON
Product-type designation   PAC3200
Size of multimeter / company-specific   size 96
Design of the product   basic
Product function    
  • voltage measurement
  Yes
  • current measurement
  Yes
  • active power measurement
  Yes
  • reactive power measurement
  Yes
  • pulse measurement
  Yes
  • frequency measurement
  Yes
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  P
  • according to DIN EN 61346-2
  P
 
Measurement:
Measuring methode    
  • for voltage measurement
  RMS
  • for current measurement
  TRMS
Type of measured value detection   complete
Curve form of the voltage   sinusoidal or distorted
Measurable line frequency Hz 45 65
Operating mode for measured value detection    
  • automatic line frequency detection
  Yes
  • set at 50 Hz
  No
  • set to 60 Hz
  No
 
Measuring inputs for voltage:
Measurable supply voltage    
  • between (PE)N and L / for AC / maximum nominal value
V 400
  • between the outer conductors / for AC / maximum nominal value
V 690
  • between (PE)N and L / for AC
V 40 480
  • between the outer conductors / for AC
V 70 831
Supply voltage / between the outer conductors / for AC    
  • maximum permissible
V 831
Measuring category / for voltage measurement   CATIII
Outer conductors and neutral conductors internal resistance    
  • for voltage measurement
M? 1.05
Power consumption / for voltage measurement    
  • per phase
mW 220
Measuring range extension for voltages    
  • with external voltage transformers
  Yes
 
Measuring inputs for current:
Measurable current    
  • 1 / for AC / nominal value
A 1
  • 2 / for AC / nominal value
A 5
Relative measurable current / for AC % 1 120
Continuous current / for AC / maximum permissible A 10
Short-time current resistance (Icw) / limited to 1 s / rated value A 100
Zero-point suppression / for current measurement   0.1 ... 10 %
Measuring category / for current measurement   CATIII
Measuring range extension for currents    
  • with external current transformers
  Yes
 
Fault limits:
Reference condition / for metering precision   according to IEC62053-22 and IEC62053-23
Formula for relative total measurement inaccuracy    
  • for measured variable voltage
  +/- 0.3 %
  • for measured variable current
  +/- 0.2 %
  • for measured variable output
  +/- 0.5 %
  • for measured variable output factor
  +/- 0.5 %
  • for measured variable reactive energy
  Class 2 according to IEC61557-12 and/or IEC62053-23
 
Supply voltage:
Design of the power supply   power supply with a wide range of voltages
Type of voltage / of supply voltage   AC/DC
Relative symmetrical tolerance / of the supply voltage % 10
Measuring category / supply voltage   CATIII
Supply voltage / 1 / at AC V 95 240
Apparent power consumption    
  • without expansion module(s) / typical
V·A 6
  • with expansion module(s) / maximum
V·A 8
Supply voltage / 1 / for DC V 110 340
 
Digital input:
Number of digital inputs   1
Input voltage / at the digital input    
  • for DC / rated value
V 24
  • final value for signal<1>-recognition
V 8
  • initial value for signal<1>-recognition
V 13
Input current / at the digital input    
  • for signal <1>
mA 7
Initial delay time / at the digital input    
  • for signal <1> after <0> / maximum
ms 5
  • for signal <0> after <1> / maximum
ms 5
 
Digital output:
Number of digital outputs   1
Design of digital outputs   switching or pulse output function
Norm / for impulse equipment   according to IEC62053-31
Pulse duration ms 30 500
Adjustable time period / minimum ms 10
Operating voltage / as ou

Назад в раздел