SIMATIC S7-400, CONTROL MODULE FM 455 C, 16 CHANNELS, CONTINUOUS 8/16 AI + 16 DI + 16 AO
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1997-08-01
    Версия от 2012-03-10
 
SIMATIC S7-400, CONTROL MODULE FM 455 C, 16 CHANNELS, CONTINUOUS 8/16 AI + 16 DI + 16 AO
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 440 mA; typ. 370 mA
Power losses
Power loss, typ. 12 W
Power loss, max. 17.3 W
Digital inputs
Number/binary inputs 16
Input characteristic curve acc. to IEC 61131, Type 2 Yes
Input voltage
Rated value, DC 24 V
for signal "0" -3 to +5 V
for signal "1" 13 to 30 V
Input current
for signal "1", typ. 7 mA
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Analog inputs
Number of analog inputs 16; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection
permissible input voltage for voltage input (destruction limit), max. 20 V
permissible input current for current input (destruction limit), max. 40 mA
Input ranges
Voltage Yes
Current Yes
Thermocouple Yes
Resistance thermometer Yes
Input ranges (rated values), voltages
0 to +10 V Yes
Input resistance (0 to 10 V) 100 k?
-1.75 to +11.75 V Yes
Input resistance (-1.75 to +11.75 V) 100 k?
-80 mV to +80 mV Yes
Input resistance (-80 mV to +80 mV) 10 M?
Input ranges (rated values), currents
0 to 20 mA Yes
Input resistance (0 to 20 mA) 50 ?
0 to 23.5 mA Yes
Input resistance (0 to 23.5 mA) 50 ?
-3.5 to +23.5 mA Yes
Input resistance (-3.5 to +23.5 mA) 50 ?
4 to 20 mA Yes
Input resistance (4 to 20 mA) 50 ?
Input ranges (rated values), thermoelements
Type B Yes
Input resistance (Type B) 10 M?
Type J Yes
Input resistance (type J) 10 M?
Type K Yes
Input resistance (Type K) 10 M?
Type R Yes
Input resistance (Type R) 10 M?
Type S Yes
Input resistance (Type S) 10 M?
Input ranges (rated values), resistance thermometers
Pt 100 Yes
Input resistance (Pt 100) 10 M?
Thermocouple (TC)
for thermocouples Type B, J, K, R, S
[nicht versorgt: TAK_ABT261_001_000]
internal temperature compensation Yes; Parameterizable
external temperature compensation with Pt100 Yes; Parameterizable
Resistance thermometer (RTD)
Characteristic linearization
for resistance thermometer Pt100 (standard)
Characteristic linearization
Parameterizable Yes
Cable length
Cable length, shielded, max. 200 m; 50 m at 80 mV and thermocouples
Analog outputs
Number of analog outputs 16
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
0 to 10 V Yes
-10 to +10 V Yes
Output ranges, current
0 to 20 mA Yes
-20 to +20 mA Yes
4 to 20 mA Yes
Connection of actuators
for voltage output 2-conductor connection Yes
for current output 2-conductor connection Yes
Load impedance (in rated range of output)
with voltage outputs, min. 1 k?
with voltage outputs, capacitive load, max. 1 µF
with current outputs, max. 500 ?
with current outputs, inductive load, max. 1 mH
Cable length
Cable length, shielded, max. 200 m; 50 m at 80 mV and thermocouples
Analog value creation
Measurement principle integrating
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 14 bit; 12 or 14 bit, parameterizable
Conversion time (per channel) 16.67 ms; for 12 bit: 16 2/3 ms for 60 Hz, 20 ms for 50 Hz; for 14 bit: 100 ms for 50 and 60 Hz
Settling time
for resistive load 0.2 ms
for capacitive load 3.3 ms
for inductive load 0.5 ms
Encoder
Connection of signal encoders
for voltage measurement Yes
for current measurement as 4-wire transducer Yes
Connectable encoders
2-wire BEROS Yes
permissible quiescent current (2-wire BEROS), max. 1.5 mA
Errors/accuracies
Linearity error (relative to input area) +/- 0,05 %
Temperature error (relative to input area) +/- 0,005 %/K
Linearity error (relative to output area) +/- 0,05 %