6ES7318-3EL01-0AB0 - SIMATIC S7-300 CPU 319-3 PN/DP, CENTRAL PROCESSING UNIT WITH 2 MBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE DP-MASTER/SLAVE, 3. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY (siemens) - Quad Industry GmbH

Артикул: 6ES7318-3EL01-0AB0
Наименование: SIMATIC S7-300 CPU 319-3 PN/DP, CENTRAL PROCESSING UNIT WITH 2 MBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE DP-MASTER/SLAVE, 3. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC S7-300 CPU 319-3 PN/DP, CENTRAL PROCESSING UNIT WITH 2 MBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE DP-MASTER/SLAVE, 3. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-08-06
SIMATIC S7-300 CPU 319-3 PN/DP, CENTRAL PROCESSING UNIT WITH 2 MBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE DP-MASTER/SLAVE, 3. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY
General information
Hardware product version 01
Firmware version V3.2
Engineering with
Programming package STEP7 V 5.5 or higher
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
External protection for supply cables (recommendation) 2 A min.
Mains buffering
Mains/voltage failure stored energy time 5 ms
Repeat rate, min. 1 s
Input current
Current consumption (rated value) 1250 mA
Current consumption (in no-load operation), typ. 500 mA
Inrush current, typ. 4 A
I²t 1.2 A²·s
Power losses
Power loss, typ. 14 W
Memory
Work memory
integrated 2048 kbyte
expandable No
Size of retentive memory for retentive data blocks 700 kbyte
Load memory
pluggable (MMC) Yes
pluggable (MMC), max. 8 Mbyte
Data management on MMC (after last programming), min. 10 a
Backup
present Yes
without battery Yes
CPU processing times
for bit operations, min. 0.0040 µs
for word operations, min. 0.01 µs
for fixed point arithmetic, min. 0.01 µs
for floating point arithmetic, min. 0.04 µs
CPU-blocks
Number of blocks (total) 4096; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
Number, max. 4096; Number range: 1 to 16000
Size, max. 64 kbyte
FB
Number, max. 4096; Number range: 0 to 7999
Size, max. 64 kbyte
FC
Number, max. 4096; Number range: 0 to 7999
Size, max. 64 kbyte
OB
Size, max. 64 kbyte
Number of free cycle OBs 1; OB 1
Number of time alarm OBs 1; OB 10
Number of delay alarm OBs 2; OB 20, 21
Number of time interrupt OBs 4; OB 32, 33, 34, 35 (OB 35: smallest settable clock pulse = 500 µs)
Number of process alarm OBs 1; OB 40
Number of DPV1 alarm OBs 3; OB 55, 56, 57
Number isochronous mode OBs 1; OB 61
Number of startup OBs 1; OB 100
Number of asynchronous error OBs 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO)
Number of synchronous error OBs 2; OB 121, 122
Nesting depth
per priority class 16
additional within an error OB 4
Counters, timers and their retentivity
S7 counter
Number 2048
Retentivity
adjustable Yes
lower limit 0
upper limit 2047
preset Z 0 to Z 7
Counting range
adjustable Yes
lower limit 0
upper limit 999
IEC counter
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
S7 times
Number 2048
Retentivity
adjustable Yes
lower limit 0
upper limit 2047
preset No retentivity
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All, max. 700 KB
Flag
Number, max. 8192 byte
Retentivity available Yes; MB 0 to MB 8191
Retentivity preset MB 0 to MB 15
Number of clock memories 8; 1 memory byte
Data blocks
Number, max. 4096; Number range: 1 to 16000
Size, max. 64 kbyte
Retentivity adjustable Yes; via non-retain property on DB
Retentivity preset Yes
Local data
per priority class, max. 32768 byte; Max. 2048 bytes per block
Address area
I/O address area
Inputs 8192 byte
Outputs 8192 byte
of which, distributed
Inputs 8192 byte
Outputs 8192 byte
Process image
Inputs 8192 byte
Outputs Назад в раздел