6ES7314-1AF10-0AB0 - SIMATIC S7-300, CPU 314 CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 48 KBYTE WORKING MEMORY MICRO MEMORY CARD NECESSARY (siemens) - Quad Industry GmbH

Артикул: 6ES7314-1AF10-0AB0
Наименование: SIMATIC S7-300, CPU 314 CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 48 KBYTE WORKING MEMORY MICRO MEMORY CARD NECESSARY (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC S7-300, CPU 314 CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 48 KBYTE WORKING MEMORY MICRO MEMORY CARD NECESSARY
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2002-09-30 2005-02-15 2005-02-15 2010-10-01
SIMATIC S7-300, CPU 314 CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 48 KBYTE WORKING MEMORY MICRO MEMORY CARD NECESSARY
General information
Hardware product version 01
Firmware version V2.0.0
Engineering with
Programming package STEP 7 V5.1 SP4 or higher
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
External protection for supply cables (recommendation) 2 A min.
Input current
Current consumption (in no-load operation), typ. 60 mA
Inrush current, typ. 2.5 A
I²t 0.5 A²·s
from supply voltage L+, max. 600 mA
Power losses
Power loss, typ. 2.5 W
Backup battery
Battery operation
Backup time, max. 1008 h; At 40 °C ambient temperature
Memory
Work memory
integrated 48 kbyte
expandable No
Load memory
pluggable (MMC) Yes
pluggable (MMC), max. 8 Mbyte
Data management on MMC (after last programming), min. 10 a
Backup
present Yes; Guaranteed by MMC (maintenance-free)
CPU processing times
for bit operations, min. 0.1 µs
for bit operations, max. 0.2 µs
for word operations, min. 0.2 µs
for fixed point arithmetic, min. 2 µs
for floating point arithmetic, min. 3 µs
CPU-blocks
Number of blocks (total) 1024; (DBs, FCs, FBs OBs, SDBs); the maximum number of loadable blocks can be reduced by the MMC being used.
DB
Number, max. 511; DB 0 reserved
Size, max. 16 kbyte
FB
Number, max. 512; From FB 0 to FB 511
Size, max. 16 kbyte
FC
Number, max. 512; from FC 0 to FC 511
Size, max. 16 kbyte
OB
Number, max. see instruction list
Size, max. 16 kbyte
Nesting depth
per priority class 8
additional within an error OB 4
Counters, timers and their retentivity
S7 counter
Number 256
of which retentive without battery
adjustable Yes
preset Z 0 to Z 7
Retentivity
adjustable Yes
Counting range
adjustable Yes
lower limit 0
upper limit 999
IEC counter
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
S7 times
Number 256
Retentivity
adjustable Yes
preset No retentivity
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All (incl. memory bits, times, counters)
Flag
Number, max. 256 byte
Retentivity available Yes; MB 0 to MB 255
Retentivity preset MB 0 to MB 15
Number of clock memories 8; 1 memory byte
Data blocks
Number, max. 511; from DB1 to DB511
Size, max. 16 kbyte
Local data
per priority class, max. 510 byte
Address area
I/O address area
Inputs 1 kbyte
Outputs 1 kbyte
Process image
Inputs 128 byte
Outputs 128 byte
Digital channels
Inputs 1024
Outputs 1024
Inputs, of which central 1024
Outputs, of which central 1024
Analog channels
Inputs 256
Outputs 256
Inputs, of which central 256
Outputs, of which central 256
Hardware configuration
Racks, max. 4
Modules per rack, max. 8
Number of DP masters
integrated 0
via CP 4
Number of operable FMs and CPs (recommended)
FM 8
CP, point-to-point 8
CP, LAN 10
Time of day
Clock
Hardware clock (real-time clock) Yes
battery-backed and synchronizable Yes
Deviation per day, max. 10 s
Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
Number 1
Number/Number range 0
Range of values 0 to 2^31 hours (when using SFC 101)
Granularity Назад в раздел