6ES7142-4BD00-0AA0 - SIMATIC DP, ELECTRONIC MODULE FOR ET200PRO, 4 DO DC 24V, 2.0A; MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY (siemens) - Quad Industry GmbH

Артикул: 6ES7142-4BD00-0AA0
Наименование: SIMATIC DP, ELECTRONIC MODULE FOR ET200PRO, 4 DO DC 24V, 2.0A; MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECTRONIC MODULE FOR ET200PRO, 4 DO DC 24V, 2.0A; MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-03-31
Manuals weitere>>
Distributed I/O device ET 200pro  2005-12-16
SIMATIC DP, ELECTRONIC MODULE FOR ET200PRO, 4 DO DC 24V, 2.0A; MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY
FH technology
Module for failsafe applications No
Supply voltage
Load voltage 2L+
Rated value (DC) 24 V
Short-circuit protection Yes; per channel, electronic
Reverse polarity protection Yes; against destruction; load increasing
Input current
from load voltage 2L+ (without load), max. 20 mA
from backplane bus 3.3 V DC, max. 20 mA
Power losses
Power loss, typ. 2 W
Address area
Address space per module
with packing 4 bit
without packing 1 byte
Digital outputs
Number/binary outputs 4
Functionality/short-circuit strength Yes; per channel, electronic
Response threshold, typ. 3
Limitation of inductive shutdown voltage to 2L+ (-47 V)
Lamp load, max. 10 W
Controlling a digital input Yes
Load resistance range
lower limit 12 Ω
upper limit 4 kΩ
Output voltage
for signal "1", min. 2L+ (-0.8 V)
Output current
for signal "1" rated value 2 A
for signal "0" residual current, max. 0.5 mA
Parallel switching of 2 outputs
for increased power No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 1 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 55 °C, max. 4 A
Cable length
Cable length, shielded, max. 30 m
Cable length unshielded, max. 30 m
Interrupts/diagnostics/status information
Diagnostic messages
Diagnostic functions Yes
Diagnostic information readable Yes
Short circuit Yes; Short-circuit of outputs to ground; module by module
Diagnostics indication LED
Group error SF (red) Yes
Status indicator digital output (green) Yes
Galvanic isolation
Galvanic isolation digital outputs
between the channels No
between the channels and the backplane bus Yes
Isolation
Isolation checked with 500 V DC
Dimensions
Width 45 mm
Height 130 mm
Depth 35 mm
Weight
Weight, approx. 140 g
Status Mar 12, 2012

Назад в раздел