6ES7141-1BF40-0AB0 - SIMATIC DP, DISTRIBUTED I/O ET200X:BASIC MOD. BM141/ECOFAST RS485; 8 DE DC 24V, 5-PIN, M12, CHANNEL DIAGNOSTICS, SHORT-CIRCUIT AND WIRE BREAK, PROCESS INTERRUPTS, INPUT DELAY:0,5MS/3MS/15MS/20MS (siemens) - Quad Industry GmbH

Артикул: 6ES7141-1BF40-0AB0
Наименование: SIMATIC DP, DISTRIBUTED I/O ET200X:BASIC MOD. BM141/ECOFAST RS485; 8 DE DC 24V, 5-PIN, M12, CHANNEL DIAGNOSTICS, SHORT-CIRCUIT AND WIRE BREAK, PROCESS INTERRUPTS, INPUT DELAY:0,5MS/3MS/15MS/20MS (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, DISTRIBUTED I/O ET200X:BASIC MOD. BM141/ECOFAST RS485; 8 DE DC 24V, 5-PIN, M12, CHANNEL DIAGNOSTICS, SHORT-CIRCUIT AND WIRE BREAK, PROCESS INTERRUPTS, INPUT DELAY:0,5MS/3MS/15MS/20MS
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-12-31 2007-10-01 2008-10-01
SIMATIC DP, DISTRIBUTED I/O ET200X:BASIC MOD. BM141/ECOFAST RS485; 8 DE DC 24V, 5-PIN, M12, CHANNEL DIAGNOSTICS, SHORT-CIRCUIT AND WIRE BREAK, PROCESS INTERRUPTS, INPUT DELAY:0,5MS/3MS/15MS/20MS
Supply voltage
Rated value (DC) 24 V
Reverse polarity protection No
Load voltage 2L+
Rated value (DC) 24 V
Reverse polarity protection No
Input current
from load voltage 1L+ (unswitched voltage) 180 mA
from load circuit 1 (unswitched voltage/supply voltage) up to 40 °C 10 A
from load circuit 1 (unswitched voltage/supply voltage) up to 55 °C 8 A
from load circuit 2 (unswitched voltage/supply voltage) up to 40 °C 10 A
from load circuit 2 (unswitched voltage/supply voltage) up to 55 °C 8 A
Power losses
Power loss, typ. 3.5 W
Hardware configuration
Expansion modules
Number of expansion modules, max. 7
of which motor starters/frequency converters, max. 6
of which, pneumatic interfaces, max. 6
Digital inputs
Number/binary inputs 8; 8 process channels DI, single channel connector
Input characteristic curve acc. to IEC 61131, Type 2 Yes
Input voltage
Rated value, DC 24 V
for signal "0" -3 to +5 V
for signal "1" 13 to 30 V
Input current
for signal "1", typ. 10 mA
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable Yes; 0.5 / 3 / 15 / 20 ms
Cable length
Cable length unshielded, max. 30 m; for signal lines
Encoder
Connectable encoders
2-wire sensor Yes
Permissible quiescent current (2-wire sensor), max. 1.5 mA
1st interface
Functionality
DP slave Yes
DP slave
Services
Direct data exchange (slave-to-slave communication) Yes; Sender
Transmission rate, min. 9.6 kbit/s
Transmission rate, max. 12 Mbit/s; 9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 12 Mbit/s
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm Yes; Parameterizable
Diagnostic messages
Wire break Yes; channel by channel
Short circuit Yes; channel by channel
Diagnostics indication LED
Group error SF (red) Yes
Galvanic isolation
Galvanic isolation No electrical isolation between the load voltages and between the load voltages and all the other circuit components
between PROFIBUS DP and all other circuit components Yes
Galvanic isolation digital inputs
between the channels No
between the channels and the backplane bus No
Degree and class of protection
IP67 Yes
Dimensions
Width 175 mm; 180 when screw mounted
Height 180 mm; 174 when screw mounted
Depth 110 mm; 90 when screw mounted
Status Mar 12, 2012