6ES7133-0BN11-0XB0 - SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 24DI 24V DC, 8DO 24V DC, 0.5A, 0.2MS INPUT DELAY, STANDARD (siemens) - Quad Industry GmbH

Артикул: 6ES7133-0BN11-0XB0
Наименование: SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 24DI 24V DC, 8DO 24V DC, 0.5A, 0.2MS INPUT DELAY, STANDARD (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 24DI 24V DC, 8DO 24V DC, 0.5A, 0.2MS INPUT DELAY, STANDARD
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-10-01 2005-10-01 2006-10-01 2015-10-01
SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 24DI 24V DC, 8DO 24V DC, 0.5A, 0.2MS INPUT DELAY, STANDARD
Hardware configuration
Rack
Required terminal block TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC
Digital inputs
Number/binary inputs 24
Input voltage
Rated value, DC 24 V
for signal "0" -30 to +5 V
for signal "1" 13 to 30 V
Input current
for signal "1", typ. 4 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", max. 0.2 ms
Cable length
Cable length unshielded, max. 100 m
Digital outputs
Number/binary outputs 8
Functionality/short-circuit strength Yes; Electronic
Output voltage
Rated value (DC) 24 V
for signal "0", max. 2 V; Idling
for signal "1", min. UE -3 V
Output current
for signal "1" permissible range for 0 to 60 °C, min. 0.5 A; in one group
for signal "0" residual current, max. 1 mA
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 8 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 60 °C, max. 2 A
Cable length
Cable length unshielded, max. 100 m
Interfaces
PROFIBUS DP
Transmission rate, max. 12 Mbit/s
Galvanic isolation
between electronic block and PROFIBUS DP Yes
Galvanic isolation digital inputs
Galvanic isolation digital inputs No
Galvanic isolation digital outputs
Galvanic isolation digital outputs Yes
Ambient conditions
Operating temperature
horizontal installation, min. 0 °C
horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure
permissible range, min. 795 hPa
permissible range, max. 1080 hPa
Relative humidity
Operation, min. 15 %
Operation, max. 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Degree and class of protection
IP20 Yes
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Status Mar 5, 2012

Назад в раздел