Input current
from supply voltage L+, max. 15 mA
Power losses
Power loss, typ. 0.7 W
Hardware configuration
Rack
Required terminal block TB 16SC
Digital outputs
Number/binary outputs 1
Controlling a digital input Yes
Output current
for signal "1" minimum load current 1 mA; Contact wiring intern: Varistor, rated voltage 275 V
Parallel switching of 2 outputs
for increased power No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 1 Hz
with inductive load, max. 0.1 Hz; with inductive load to IEC 947-5-1, 13 DC /15 AC
on lamp load, max. 0.1 Hz
mechanical, max. 10 Hz
Relay outputs
Rated input voltage of relay coil L+ (DC) 24 V
Reverse polarity protection Yes
Switching capacity of contacts
with inductive load, max. 2 A; 0.2 to 2 A (with inductive load complying with IEC 947-5-1 13 V DC/15 V AC)
Switching frequency/contacts/at ohmic load/maximum 5 A; 0.2 to 5 A
Thermal continuous current, max. 5 A
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Interrupts/diagnostics/status information
Alarms
Alarms No
Diagnostic messages
Diagnostic functions No
Diagnostics indication LED
Status indicator digital output (green) Yes
Galvanic isolation
Galvanic isolation digital outputs
between channels and power supply of relays Yes
between the channels and the backplane bus Yes
Permissible potential difference
between M internally or supply voltage of relays and the outputs 240 V AC
between M internally and supply voltage of relays 75 VDC / 60 VAC
Isolation
tested with
between M internally or supply voltage of relays and the outputs 2500 V DC
between M internally and supply voltage of relays 1500 V AC
Dimensions
Width 10 mm
Height 64 mm
Depth 51 mm
Required slots 1; from 8
Weight
Weight, approx. 30 g