6ES7122-1FA00-0AA0 - SIMATIC SC,ELECTRONIC SUBMODULE 1 DO, AC 115/230 V (siemens) - Quad Industry GmbH

Артикул: 6ES7122-1FA00-0AA0
Наименование: SIMATIC SC,ELECTRONIC SUBMODULE 1 DO, AC 115/230 V (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC SC,ELECTRONIC SUBMODULE 1 DO, AC 115/230 V
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-10-01 2005-10-01 2006-10-01 2015-10-01
SIMATIC SC,ELECTRONIC SUBMODULE 1 DO, AC 115/230 V
Supply voltage
Load voltage L1
Rated value (AC) 230 V; 120/230 V AC
permissible frequency range, lower limit 47 Hz
permissible frequency range, upper limit 63 Hz
Power losses
Power loss, typ. 0.7 W
Hardware configuration
Rack
Required terminal block TB 16SC
Digital outputs
Number/binary outputs 1
Size of motor starter, max. Size 8
Functionality/short-circuit strength No
Lamp load, max. 100 W; at AC 230 V: 100 W, at AC 120 V: 50 W
Zero-crossing switch Yes
Controlling a digital input Yes; Only with additional load
Output voltage
for signal "1", min. L+ (-1 V)
Output current
for signal "1" rated value 1 A
for signal "1" permissible range for 0 to 40 °C, min. 40 mA
for signal "1" permissible range for 0 to 40 °C, max. 1.1 A
for signal "1" permissible range for 40 to 60 °C, min. 40 mA
for signal "1" permissible range for 40 to 60 °C, max. 0.6 A
for signal "1" permissible surge current, max. 10 A; for 2 half waves
for signal "0" residual current, max. 3 mA
Output delay with resistive load
0 to "1", max. 20 ms
1 to "0", max. 30 ms
Parallel switching of 2 outputs
for increased power No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 50 Hz
with inductive load, max. 10 Hz; with inductive load to IEC 947-5-1, 13 DC /15 AC
on lamp load, max. 1 Hz
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Interrupts/diagnostics/status information
Alarms
Alarms No
Diagnostic messages
Diagnostic functions No
Diagnostics indication LED
Status indicator digital output (green) Yes
Galvanic isolation
Galvanic isolation digital outputs
between the channels and the backplane bus Yes
Permissible potential difference
between M internally and the inputs 240 V AC
Isolation
Isolation checked with 2500 V DC
Dimensions
Width 10 mm
Height 64 mm
Depth 51 mm
Required slots 1; from 8
Weight
Weight, approx. 15 g
Status Mar 5, 2012