| CIRCUIT BREAKER 3VT4 HIGH SWITCHING CAPACITY ICU=65KA, 415V AC 3-POLE; CIRCUIT BREAKER W/O ELECTRONIC TRIP UNIT W/O AUXILIARY TRIP UNIT W/O AUXILIARY/ALARM SWITCH WITHOUT AUXILIARY RELEASE WITHOUT AUXILIARY/ALARM SWITCH OHNE HILFS/ALARMSCHALTER |
| |
| Technical data: | | |
| Width | mm | 210 |
| Height | mm | 494 |
| Depth | mm | 157 |
| Product function / ground-fault protection | | No |
| Continuous current / rated value | A | 1,000 |
| Operating voltage / for main current circuit | | |
- at 50 Hz / for AC / maximum
| V | 690 |
- at 60 Hz / for AC / maximum
| V | 690 |
| | V | 440 |
| Impulse voltage resistance / rated value | kV | 8 |
| Number of poles | | 3 |
| Active power loss / maximum | W | 100 |
| Operating cycles / maximum | 1/h | 120 |
| Operating frequency | | |
| | Hz | 50 |
| | Hz | 60 |
| Breaking capacity limit short-circuit current (lcu) | | |
| | kA | 85 |
| | kA | 65 |
| | kA | 45 |
| | kA | 20 |
| Breaking capacity operating short-circuit current (lcs) | | |
| | kA | 45 |
| | kA | 36 |
| | kA | 30 |
| | kA | 20 |
| Pouvoir d'enclenchement courant de court-circuit (Icm) / ? 415 V / valeur assign?e | kA | 140 |
| Type of mounting | | fixed mounting |
| Design of the electrical connection / for main current circuit | | without connection accessoires |
| Arrangement of electrical connectors / for main current circuit | | front side |
| Number of NC contacts / for auxiliary contacts | | 0 |
| Number of NO contacts / for auxiliary contacts | | 0 |
| Number of change-over switches / for auxiliary contacts | | 0 |
| Product component | | |
- undervoltage release mechanism
| | No |
| | | No |
- undervoltage release with leading contact
| | No |
| Compatibilit? d'utilisation / sectionneur | | Yes |
| Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | Q |
- according to DIN EN 61346-2
| | Q |
| Ambient temperature | | |
| | | |
| | °C | -40 |
| | °C | 70 |
| | | |
| | °C | -40 |
| | °C | 70 |
| Derating temperature / for the rated value of the continuous current | °C | 50 |
| Protection class IP | | IP40 |
| Product function | | |
| | | No |
- for zero conductors / short-circuit and overload protection
| | No |
| Built in orientation | | with vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back |
| Mechanical operating cycles as operating time / typical | | 10,000 |
| Electrical operating cycles as operating time / typical | | 4,000 |
| |
| Certificates/approvals: |
| |
| |
| Further information: |
| Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/lowvoltage/catalogs |
| Industry Mall (Online-Bestellsystem) http://www.siemens.com/lowvoltage/mall |
| Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/3VT4710-3AA30-0AA0/all |
| Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VT4710-3AA30-0AA0 |
| CAx-Online-Generator http://www.siemens.com/cax |
| |
| |
| |
| last change: | Feb 28, 2012 |