| CONTACTOR, AC-3, 15KW/400V, 1NO+1NC, AC 110V 50HZ, 3-POLE, SZ S0 SCREW TERMINAL |
|
General technical data: |
product brand name | | SIRIUS |
Size of the contactor | | S0 |
Product extension / auxiliary switch | | Yes |
Protection class IP / on the front | | IP20 |
Protection against electrical shock | | finger-safe |
Degree of pollution | | 3 |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Ambient temperature / during storage | °C | -55… +80 |
Ambient temperature / during operating | °C | -25… +60 |
Shock resistance | | |
| | |
| | 8,3g / 5 ms, 5,3g / 10 ms |
| | |
| | 13,5g / 5 ms, 8,3g / 10 ms |
Impulse voltage resistance / rated value | kV | 6 |
Insulation voltage / rated value | V | 690 |
Mechanical operating cycles as operating time | | |
- of the contactor / typical
| | 10,000,000 |
- of the contactor with added auxiliary switch block / typical
| | 10,000,000 |
- of the contactor with added electronics-compatible auxiliary switch block / typical
| | 5,000,000 |
|
Main circuit: |
Number of NC contacts / for main contacts | | 0 |
Number of NO contacts / for main contacts | | 3 |
Operating current | | |
| | |
- at 40 °C ambient temperature / rated value
| A | 50 |
- at 60 °C ambient temperature / rated value
| A | 42 |
- at AC-2 / at 400 V / rated value
| A | 32 |
- at AC-3 / at 400 V / rated value
| A | 32 |
- at AC-4 / at 400 V / rated value
| A | 22 |
Operating current | | |
- with 1 current path / at DC-1
| | |
| A | 35 |
| A | 4.5 |
- with 2 current paths in series / at DC-1
| | |
| A | 35 |
| A | 35 |
- with 3 current paths in series / at DC-1
| | |
| A | 35 |
| A | 35 |
- with 1 current path / at DC-3 / at DC-5
| | |
| A | 20 |
| A | 2.5 |
- with 2 current paths in series / at DC-3 / at DC-5
| | |
| A | 35 |
| A | 15 |
- with 3 current paths in series / at DC-3 / at DC-5
| | |
| A | 35 |
| A | 35 |
Service power | | |
- at AC-2 / at 400 V / rated value
| kW | 15 |
- at AC-3 / at 400 V / rated value
| kW | 15 |
- at AC-4 / at 400 V / rated value
| kW | 11 |
Active power loss / per conductor / typical | W | 2.7 |
Off-load operating frequency | | |
| 1/h | 5,000 |
| 1/h | 1,500 |
Frequency of operation / at AC-1 / according to IEC 60947-6-2 | 1/h | 1,000 |
Frequency of operation / at AC-2 / according to IEC 60947-6-2 | 1/h | 750 |
Frequency of operation / at AC-3 / according to IEC 60947-6-2 | 1/h | 750 |
Frequency of operation / at AC-4 / according to IEC 60947-6-2 | 1/h | 250 |
|
Control circuit: |
Type of voltage / of the controlled supply voltage | | AC |
Control supply voltage / 1 | | |
- at 50 Hz / for AC / rated value
| V | 110 |
operating range factor control supply voltage rated value / of the magnet coil | | |
| | 0.8… 1.1 |
Apparent pull-in power / of the solenoid / for AC | V·A | 77 |
Apparent holding power / of the solenoid / for AC | V·A | 9.8 |
Inductive power factor | | |
- with the pull-in power of the coil
| | 0.82 |
- with the pull-in power of the coil
| | 0.25 |
Closing delay | | |
| ms | 8… 40 |
Opening delay | | |
| ms | 4… 16 |
Arcing time | ms | 10… 10 |
|
Auxiliary circuit: |
Contact reliability / of the auxiliary contacts | | 1 faulty switching per 100 million (17 V, 1 mA) |
Number of NC contacts / for auxiliary contacts / instantaneous switching | | 1 |
Number of NO contacts / for auxiliary contacts / instantaneous switching | | 1 |
Operating current / of the auxiliary contacts | | |
| A | 10 |
| | |
|