3RK3131-2AC10 - SIRIUS, CENTRAL MODULE 3RK3 ADVANCED FOR MODULAR SAFETY SYSTEM 3RK3 4/8 F-DI, 1F-RO, 1 F-DO, 24 V DC MONITORING OF ASI SLAVES, CONTROL OF SAFE OUTPUTS ON AS-I BUS PARAMETERIZABLE VIA SW MSS ES WIDTH 45MM SPRING-LOADED TERMINAL UP TO CATEGORY 4 (EN954-1) UP TO SIL3 (IEC 61508) UP TO PERFORMANCE LEVEL E (ISO 13849-1) (siemens) - Quad Industry GmbH

Артикул: 3RK3131-2AC10
Наименование: SIRIUS, CENTRAL MODULE 3RK3 ADVANCED FOR MODULAR SAFETY SYSTEM 3RK3 4/8 F-DI, 1F-RO, 1 F-DO, 24 V DC MONITORING OF ASI SLAVES, CONTROL OF SAFE OUTPUTS ON AS-I BUS PARAMETERIZABLE VIA SW MSS ES WIDTH 45MM SPRING-LOADED TERMINAL UP TO CATEGORY 4 (EN954-1) UP TO SIL3 (IEC 61508) UP TO PERFORMANCE LEVEL E (ISO 13849-1) (siemens)
Производитель: Siemens


Наименование продукта
SIRIUS, CENTRAL UNIT 3RK3 ADVANCED FOR MODULAR SAFETY SYSTEM 3RK3 4/8 F-DI, 1F-RO, 1 F-DO, 24 VDC MONITORING OF ASI SLAVES, CONTROL OF 12 SAFE OUTPUTS ON AS-I BUS PARAMETERIZABLE VIA SW MSS ES WIDTH 45MM SPRING-LOADED TERMINAL UP TO CATEGORY 4 (EN954-1) UP TO SIL3 (IEC 61508) UP TO PERFORMANCE LEVEL E (ISO 13849-1) 9 EXPANSION MODULES CONNECTABLE
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2011-08-04
    Версия от 2012-04-21
 
SIRIUS, CENTRAL UNIT 3RK3 ADVANCED FOR MODULAR SAFETY SYSTEM 3RK3 4/8 F-DI, 1F-RO, 1 F-DO, 24 VDC MONITORING OF ASI SLAVES, CONTROL OF 12 SAFE OUTPUTS ON AS-I BUS PARAMETERIZABLE VIA SW MSS ES WIDTH 45MM SPRING-LOADED TERMINAL UP TO CATEGORY 4 (EN954-1) UP TO SIL3 (IEC 61508) UP TO PERFORMANCE LEVEL E (ISO 13849-1) 9 EXPANSION MODULES CONNECTABLE
 
General technical data:
product brand name   SIRIUS
product designation   Modular Safety System 3RK3
Design of the product   Central module - Advanced
Protection class IP   IP20
Resistance against shock   15g / 11 ms
Degree of pollution   3
Built in orientation   vertical
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during operating
°C -20 +60
  • during storage
°C -40 +85
  • during transport
°C -40 +85
Relative humidity    
  • during operating phase
% 95 10
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4   2 kV (power ports)
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5   2 kV
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5   1 kV
Electrostatic discharge / according to IEC 61000-4-2   4 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling / according to IEC 61000-4-3   10 V/m, 3 V/m, 1 V/m
Impulse voltage resistance / rated value V 2,500
Insulation voltage / rated value V 300
Item designation / according to DIN 40719 extendable after IEC 204-2 / according to IEC 750   K
Item designation / according to DIN EN 61346-2   K
Product function    
  • EMERGENCY STOP function
  Yes
  • protective door monitoring
  Yes
  • protective door monitoring with tumbler
  Yes
  • muting, 2 sensor parallel
  Yes
  • muting, 4 sensor parallel
  Yes
  • muting, 4 sensor sequential
  Yes
  • monitoring parameterizable
  Yes
  • evaluation: contact-free acting protection device
  Yes
  • evaluation: selector switch
  Yes
  • step mat monitoring
  Yes
  • evaluation: two-hand control panel
  Yes
  • evaluation: enabling switch
  Yes
  • monitored start-up
  Yes
Protocol / will be supported / PROFIBUS DP protocol   No
Protocol / optional / will be supported / PROFIBUS DP protocol   Yes
 
Control circuit:
type of voltage   DC
Control supply voltage / 1 / for DC / rated value V 24
Operating range factor control supply voltage rated value    
  • of the solenoid
  0.85 1.15
 
Auxiliary circuit:
Product function    
  • inputs parameterisable
  Yes
  • outputs parameterisable
  Yes
Number of inputs    
  • safety-related
  8
  • not safety-related
  0
Number of outputs    
  • as contact-affected switching element / safety-related
   
  • 1-channel
  1
  • 2-channel
  0
  • as contact-less semiconductor switching element
   
  • safety-related / 2-channel
  1
  • not safety-oriented / 2-channel
  0
  • to the test of contact afflicated sensors
  2
 
Short-circuit:
Design of the fuse link / for short-circuit protection of the contact afflicted switching element / required   NH Typ 3NA, DIAZED Typ 5SB, NEOZED Typ 5SE
 
Installation/mounting/dimensions:
Type of mounting   standard rail
Width mm 45
Height mm 113
Depth mm 124
 
Connections:
Product function / removable terminal for auxiliary and control circuit   Yes
Design of the electrical connection / for auxiliary and control current circuit   spring-loaded terminals
Conductor cross-section that can be connected / for auxiliary contact    
  • solid
mm? 0.25 1.5
  • stranded wire
   
  • with conductor end processing
mm? 0.25 1.5
  • without conductor final cutting
mm? / 0.25
AWG number / as coded connectable conductor cross-section    
  • for auxiliary contact
  20 16
Type of the connectable conductor cross-section / for auxiliary contacts    
  • solid
  2x (0.25 ... 1.5 mm?)
  • finely stranded
   
  • with conductor end processing
  2x (0.25 ... 1.5 mm?)
  • without conductor final cutting
  2x (0.25 ... 1.5 mm?)
Type of the connectable conductor cross-section / for AWG conductors    
  • for auxiliary contacts
  2x (20 ... 16)
 
Certificates/approvals:
Назад в раздел