| SIRIUS, EXPANSION MODULE 3RK32 FOR 3RK3 MODULAR SAFETY SYSTEM 4 F-DO, DC 24V/1.5A PARAMETERIZABLE VIA SW MSS ES 22.5MM WIDTH SCREW TERMINAL UP TO CATEGORY 4 (EN954-1) UP TO SIL3 (IEC 61508) UP TO PERFORMANCE LEVEL E (ISO 13849-1) |
|
General technical data: |
product brand name | | SIRIUS |
product designation | | Modular Safety System 3RK3 |
Protection class IP | | IP20 |
Resistance against shock | | 15g / 11 ms |
Degree of pollution | | 3 |
Built in orientation | | vertical |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Ambient temperature | | |
| °C | -40… +85 |
| °C | -20… +60 |
| °C | -40… +85 |
Relative humidity | | |
| % | 10… 95 |
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV (power ports) |
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5 | | 2 kV |
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5 | | 1 kV |
Electrostatic discharge / according to IEC 61000-4-2 | | 4 kV contact discharge / 8 kV air discharge |
Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m, 3 V/m, 1 V/m |
Impulse voltage resistance / rated value | V | 500 |
Insulation voltage / rated value | V | 50 |
Item designation / according to DIN 40719 extendable after IEC 204-2 / according to IEC 750 | | K |
Item designation / according to DIN EN 61346-2 | | K |
Product function | | |
| | No |
- protective door monitoring
| | No |
- evaluation: contact-free acting protection device
| | No |
- evaluation: selector switch
| | No |
| | No |
- evaluation: two-hand control panel
| | No |
- evaluation: enabling switch
| | No |
| | No |
|
Control circuit: |
type of voltage | | DC |
Control supply voltage / 1 / for DC / rated value | V | 24 |
Operating range factor control supply voltage rated value | | |
| | 0.85… 1.15 |
|
Auxiliary circuit: |
Type of the safety-related wiring | | |
| | Yes |
Number of inputs | | |
| | 0 |
| | 0 |
Number of outputs | | |
- as contact-affected switching element / safety-related
| | |
| | 0 |
| | 0 |
- as contact-less semiconductor switching element
| | |
- safety-related / 2-channel
| | 4 |
- not safety-oriented / 2-channel
| | 0 |
- to the test of contact afflicated sensors
| | 0 |
|
|
Installation/mounting/dimensions: |
Type of mounting | | standard rail |
Width | mm | 22.5 |
Height | mm | 102 |
Depth | mm | 124 |
|
Connections: |
Product function / removable terminal for auxiliary and control circuit | | Yes |
Design of the electrical connection / for auxiliary and control current circuit | | screw-type terminals |
Conductor cross-section that can be connected / for auxiliary contact | | |
| mm? | 0.5… 4 |
| | |
- with conductor end processing
| mm? | 0.5… 2.5 |
|
Certificates/approvals: |
General Product Approval | Functional Safety / Safety of Machinery | | |
| |
|
last change: | Apr 13, 2012 |