art.1SBL367201R1300 - AF52-40-00-13 100-250V50/60HZ-DC Contactor (AF52 4-pole contactors are used for controlling power circuits up to 690 V AC and 440 V DC. They are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...). AF... con | Quad Industry GmbH

Àðòèêóë: 1SBL367201R1300
Íàèìåíîâàíèå: AF52-40-00-13 100-250V50/60HZ-DC Contactor (AF52 4-pole contactors are used for controlling power circuits up to 690 V AC and 440 V DC. They are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...). AF... contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V DC. AF contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF contactors have built-in surge protection and do not require additional surge suppressors. The AF... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC operated - Accessories: a wide range of accessories is available.)
Ïðîèçâîäèòåëü: ABB


AF52-40-00-13

General Information

  • Extended Product Type:
    AF52-40-00-13
  • Product ID:
    1SBL367201R1300
  • EAN:
    3471523133631
  • Catalog Description:
    AF52-40-00-13 100-250V50/60HZ-DC Contactor
  • Long Description:
    AF52 4-pole contactors are used for controlling power circuits up to 690 V AC and 440 V DC. They are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...). AF... contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V DC. AF contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF contactors have built-in surge protection and do not require additional surge suppressors. The AF... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC operated - Accessories: a wide range of accessories is available.

Ordering

  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Popular Downloads

Dimensions

  • Product Net Width:
    70 mm
  • Product Net Depth:
    113.5 mm
  • Product Net Height:
    125.5 mm
  • Product Net Weight:
    1.16 kg

Technical

  • Number of Main Contacts NO:
    4
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    0
  • Number of Auxiliary Contacts NC:
    0
  • Rated Operational Voltage:
    Main Circuit 690 V
  • Rated Frequency (f):
    Main Circuit 50 / 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 ??C 105 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 ??C 100 A
    (690 V) 60 ??C 80 A
    (690 V) 70 ??C 70 A
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 60 ??C 53 A
    (380 / 400 V) 60 ??C 53 A
    (415 V) 60 ??C 53 A
    (440 V) 60 ??C 53 A
    (500 V) 60 ??C 45 A
    (690 V) 60 ??C 35 A
  • Rated Operational Power AC-3 (Pe):
    (220 / 230 / 240 V) 15 kW
    (380 / 400 V) 22 kW
    (415 V) 30 kW
    (440 V) 30 kW
    (500 V) 30 kW
    (690 V) 30 kW
  • Rated Short-time Withstand Current (Icw):
    at 40 ??C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
    at 40 ??C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
    at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
    at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
    at 40 ??C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
  • Maximum Electrical Switching Frequency:
    AC-1 600 cycles per hour
  • Rated Insulation Voltage (Ui):
    acc. to UL/CSA 600 V
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
  • Rated Impulse Withstand Voltage (Uimp):
    6 kV
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Rated Control Circuit Voltage (Uc):
    50 Hz 100 ... 250 V
    60 Hz 100 ... 250 V
    DC Operation 100 ... 250 V
  • Connecting Capacity Main Circuit:
    Flexible with Ferrule 1/2x 4...35 mm??
    Rigid 1/2x 6...35 mm??
  • Connecting Capacity Control Circuit:
    Flexible with Ferrule 1/2x 0.75 ... 2.5 mm??
    Rigid 1/2x 1 ... 2.5 mm??
  • Wire Stripping Length:
    Main Circuit 16 mm
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
  • Terminal Type:
    Screw Terminals

Environmental

  • Ambient Air Temperature:
    Close to Contactor for Storage -60...+80 ??C
    Near Contactor for Operation in Free Air -40 ... +70 ??C
  • Climatic Withstand:
    Category B according to IEC 60947-1 Annex Q
  • Maximum Operating Altitude Permissible:
    3000 m
  • Resistance to Vibrations acc. to IEC 60068-2-6:
    5 ... 300 Hz 3 g Closed position / 2 g Open position

Technical UL/CSA

  • General Use Rating UL/CSA:
    (600 V AC) 80 A
  • Horsepower Rating UL/CSA:
    (120 V AC) Single Phase 3 Hp
    (240 V AC) Single Phase 10 Hp
    (200 ... 208 V AC) Three Phase 15 Hp
    (220 ... 240 V AC) Three Phase 20 Hp
    (440 ... 480 V AC) Three Phase 40 Hp
    (550 ... 600 V AC) Three Phase 50 Hp

Certificates and Declarations (Document Number)

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    150 mm
  • Package Level 1 Length:
    150 mm
  • Package Level 1 Height:
    103 mm
  • Package Level 1 Gross Weight:
    1.27 kg
  • Package Level 1 EAN:
    3471523133631
  • Package Level 2 Units:
    8 piece
  • Package Level 2 Width:
    250 mm
  • Package Level 2 Length:
    300 mm
  • Package Level 2 Height:
    300 mm
  • Package Level 3 Units:
    192 piece

Classifications

  • Object Classification Code:
    Q
  • E-nummer:
    3210311
  • ETIM 4:
    EC000066 - Magnet contactor, AC-switching
  • ETIM 5:
    EC000066 - Magnet contactor, AC-switching
  • ETIM 6:
    EC000066 - Power contactor, AC switching
  • UNSPSC:
    39121529




Image 0 alt text

Categories

  • Products ?? Low Voltage Products and Systems ?? Control Products ?? Contactors ?? Block Contactors