art.GJL1213913R9031 - VBC6A-30-01-F-91 Mini Reversing Contactor (VBC6-30-01-F-24 Mini Rev. Contactor 24VDC, w/o Cover) | Quad Industry GmbH

Àðòèêóë: GJL1213913R9031
Íàèìåíîâàíèå: VBC6A-30-01-F-91 Mini Reversing Contactor (VBC6-30-01-F-24 Mini Rev. Contactor 24VDC, w/o Cover)
Ïðîèçâîäèòåëü: ABB


VBC6A-30-01-F-91

General Information

  • Extended Product Type:
    VBC6A-30-01-F-91
  • Product ID:
    GJL1213913R9031
  • EAN:
    4013614053870
  • Catalog Description:
    VBC6A-30-01-F-91 Mini Reversing Contactor
  • Long Description:
    VBC6-30-01-F-24 Mini Rev. Contactor 24VDC, w/o Cover

Ordering

  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85365080

Popular Downloads

Dimensions

  • Product Net Width:
    96.5 mm
  • Product Net Height:
    57.5 mm
  • Product Net Depth:
    46.5 mm
  • Product Net Weight:
    0.345 kg

Technical

  • Contactor Starter Type:
    Compact Reversing Contactor with Mechanical Interlock and Safety Blocking
  • Number of Auxiliary Contacts NC:
    1
  • Number of Auxiliary Contacts NO:
    0
  • Number of Main Contacts NC:
    0
  • Number of Main Contacts NO:
    3
  • Number of Poles:
    4
  • Pollution Degree:
    3
  • Rated Frequency (f):
    Control Circuit DC
  • Rated Impulse Withstand Voltage (Uimp):
    Main Circuit 6 kV
  • Rated Insulation Voltage (Ui):
    690 V
    acc. to UL/CSA 600 V
  • Rated Operational Current AC-1 (Ie):
    (220 / 240 V) 40 °C 20 A
    (220 / 240 V) 55 °C 16 A
    (380 / 440 V) 40 °C 20 A
    (380 / 440 V) 55 °C 16 A
    (690 V) 40 °C 6 A
    (690 V) 55 °C 6 A
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 55 °C 9 A
    (380 / 400 V) 55 °C 8.5 A
    (440 V) 55 °C 8 A
    (500 V) 55 °C 5.5 A
    (690 V) 55 °C 3.5 A
  • Rated Operational Voltage:
    Auxiliary Circuit 12 ... 240 V DC
    Auxiliary Circuit 12 ... 500 V AC
    Main Circuit 12 ... 690 V AC
  • Degree of Protection:
    Control Circuit Terminals IP20
    Main Circuit Terminals IP20
  • Mechanical Durability:
    10000000 cycle
  • Connecting Capacity Main Circuit:
    Flexible with Ferrule 1/2x 1 ... 2.5 mm²
    Flexible 1/2x 1 ... 2.5 mm²
    Rigid 1/2x 1 ... 4 mm²
  • Mounting on DIN Rail:
    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
  • Standards:
    IEC/EN 60947-1
    IEC/EN 60947-4-1

Environmental

  • Resistance to Shock acc. to IEC 60068-2-27:
    11 ms Pulse 15g
  • Resistance to Vibrations acc. to IEC 60068-2-6:
    5g / 5 ... 150 Hz
  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:
    Main Circuit 600 V AC
  • Horsepower Rating UL/CSA:
    (208 V AC) Three Phase 1 Hp
    (220 ... 240 V AC) Single Phase 0.5 Hp
    (220 ... 240 V AC) Three Phase 2 Hp
    (440 ... 480 V AC) Three Phase 3 Hp
    (550 ... 600 V AC) Three Phase 1 Hp

Certificates and Declarations (Document Number)

Container Information

  • Package Level 1 Units:
    5 piece
  • Package Level 1 Width:
    115 mm
  • Package Level 1 Height:
    54 mm
  • Package Level 1 Length:
    280 mm
  • Package Level 1 Gross Weight:
    1.795 kg
  • Package Level 1 EAN:
    4013614416361

Classifications

  • Object Classification Code:
    Q
  • ETIM 5:
    EC000010 - Starter combination
  • ETIM 6:
    EC000010 - Combination of contactors
  • eClass:
    7.0 27371009




Image 0 alt text

Categories

  • Products >> Low Voltage Products and Systems >> Control Products >> Contactor Starters >> Reversing Contactors


Íàçàä â ðàçäåë