art.GJH1213063R5315 - TKC6-31Z-F-55 Mini Contactor Relay 50-90VDC (The TKC6-31Z-F mini contactor relay is a compact 4 pole contactor relay with flat pin connection. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors | Quad Industry GmbH
Àðòèêóë: GJH1213063R5315
Íàèìåíîâàíèå: TKC6-31Z-F-55 Mini Contactor Relay 50-90VDC (The TKC6-31Z-F mini contactor relay is a compact 4 pole contactor relay with flat pin connection. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors relays are used in residential buldings, commercial buildings and industrial applications for switching of control signals up to 3 A / 400 V (AC-15). Further features are the noiseless and hum-free coil and a a switch position indication.)
Ïðîèçâîäèòåëü: ABB
TKC6-31Z-F-55
General Information
Extended Product Type:
TKC6-31Z-F-55
Product ID:
GJH1213063R5315
EAN:
4013614407239
Catalog Description:
TKC6-31Z-F-55 Mini Contactor Relay 50-90VDC
Long Description:
The TKC6-31Z-F mini contactor relay is a compact 4 pole contactor relay with flat pin connection. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors relays are used in residential buldings, commercial buildings and industrial applications for switching of control signals up to 3 A / 400 V (AC-15). Further features are the noiseless and hum-free coil and a a switch position indication.
Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC Control Circuit DC Main Circuit 60 Hz Main Circuit 50 Hz Main Circuit DC
Rated Impulse Withstand Voltage (Uimp):
Auxiliary Circuit 6 kV
Rated Insulation Voltage (Ui):
690 V acc. to UL/CSA 600 V
Number of Main Contacts NC:
0
Number of Main Contacts NO:
0
Number of Auxiliary Contacts NC:
1
Number of Auxiliary Contacts NO:
3
Rated Operational Current AC-15 (Ie):
(120 V) 4 A (220 / 240 V) 4 A (240 V) 4 A (24 V) 4 A (380 / 400 V) 3 A (500 V) 2 A
Rated Operational Current DC-13 (Ie):
(110 V) 0.7 A (220 / 240 V) 0.4 A (24 V) 2.5 A
Conventional Free-air Thermal Current (Ith):
Auxiliary Circuit 6 A
Rated Control Circuit Voltage (Uc):
50 ... 90 V DC
Coil Operating Limits:
(acc. to IEC 60947-4-1) for DC supply Uc Min. ... Uc Max. (at θ ≤ 55 °C) (acc. to IEC 60947-5-1) for DC supply Uc Min. ... Uc Max. (at θ ≤ 55 °C)
Degree of Protection:
Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20
Mechanical Durability:
10000000 cycle
Maximum Electrical Switching Frequency:
AC-15 600 cycles per hour DC-13 600 cycles per hour
Mounting on DIN Rail:
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Standards:
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1
Remarks:
No CA6 or CAF6 mountable
Environmental
Ambient Air Temperature:
Operation -30 ... +70 °C Storage -40 ... +85 °C
Maximum Operating Altitude Permissible:
2000 m
Resistance to Shock acc. to IEC 60068-2-27:
11 ms Pulse 15g
Resistance to Vibrations acc. to IEC 60068-2-6:
3g / 3 ... 150 Hz
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment