art.FPL1813001R0017 - CONTACTOR | Quad Industry GmbH

Àðòèêóë: FPL1813001R0017
Íàèìåíîâàíèå: CONTACTOR
Ïðîèçâîäèòåëü: ABB


BC16-30-01 12V DC

General Information

  • Extended Product Type:
    BC16-30-01 12V DC
  • Product ID:
    FPL1813001R0017
  • EAN:
    3471521180071
  • Catalog Description:
    CONTACTOR

Ordering

  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Popular Downloads

Dimensions

  • Product Net Weight:
    0.540 kg

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    0
  • Number of Auxiliary Contacts NC:
    1
  • Standards:
    Devices complying with international standards IEC 947-1 / 947-4-1 and European standards EN 60 947-1 / 947-4-1. Electromagnetic compatibility (EMC) acording to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1
  • Rated Operational Voltage:
    Main Circuit 690 V
  • Rated Frequency (f):
    Supply Circuit 50 Hz
    Supply Circuit 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    q = 40 °C 10.0 A
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 28 A
    acc. to IEC 60947-5-1, q = 40 °C 10 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 °C 28 A
    (690 V) 55 °C 25 A
    (690 V) 70 °C 23 A
  • Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
    8 x Ie AC-3
  • Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
    10 x Ie AC-3
  • Rated Operational Current AC-15 (Ie):
    (220 / 240 V) 4 A
    (24 / 127 V) 6 A
    (380 / 440 V) 3 A
    (500 V) 2 A
    (690 V) 2 A
  • Short-Circuit Protective Devices:
    Auxiliary Circuit - gG Type Fuses 10 A
    gG Type Fuses 32 / 35 A
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 130 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 28 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 50 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 280 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 70 A
    for 0.1 s 100 A
    for 1 s 50 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 200 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 120 A
  • Maximum Electrical Switching Frequency:
    AC-1 600 cycles per hour
    AC-2 / AC-4 300 cycles per hour
    AC-3 1200 cycles per hour
  • Rated Operational Current DC-13 (Ie):
    (125 V) 1.1 / 138 A
    (24 V) 6 / 144 A
    (250 V) 0.55 / 138 A
    (48 V) 2.8 / 134 A
    (72 V) 2 / 144 A
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
    acc. to UL/CSA 600 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Mechanical Durability:
    10 million
  • Maximum Mechanical Switching Frequency:
    6000 cycles per hour
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C
  • Rated Control Circuit Voltage (Uc):
    DC Operation 12 V
  • Coil Consumption:
    Average Holding Value, from Warm State 7 W
    Average Pull-in Value, from Cold State 7 W
  • Operate Time:
    Between Coil Energization and NO Contact Closing 50 ... 75 ms
    Between Coil De-energization and NO Contact Opening 15 ... 30 ms
    Between Coil De-energization and NC Contact Closing 17 ... 32 ms
    Between Coil Energization and NC Contact Opening 45 ... 70 ms
  • Mounting on DIN Rail:
    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
  • Mounting by Screws (not supplied):
    2 x M 4
  • Connecting Capacity Main Circuit:
    Rigid Cable 1 ... 4 mm²
    Flexible with Cable End 0.75 ... 2.5 mm²
  • Connecting Capacity Auxiliary Circuit:
    Rigid Cable 1 ... 4 mm²
    Flexible with Cable End 0.75 ... 2.5 mm²
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10
  • Connecting terminals (delivered in open position) Main poles:
    M 3.5 (+,-) pozidriv 2 screws with cable clamp

Environmental

  • Ambient Air Temperature:
    Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
    Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C
    Close to Contactor without Thermal O/L Relay (Uc) -55 ... +70 °C
    Close to Contactor for Storage -60 ... +80 °C
  • Climatic Withstand:
    acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
  • Maximum Operating Altitude Permissible:
    3000 m
  • Resistance to Shock acc. to IEC 60068-2-27:
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 m/s²
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 20 m/s²
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 m/s²
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 20 m/s²
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 20 m/s²
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 20 m/s²
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 m/s²

Certificates and Declarations (Document Number)

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    44 mm
  • Package Level 1 Height:
    81 mm
  • Package Level 1 Gross Weight:
    0.540 kg

Classifications

  • UNSPSC:
    39121529




Image 0 alt text
Image 1 alt text
Image 2 alt text
Image 3 alt text
Image 4 alt text
Image 5 alt text

Categories

  • Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors


Íàçàä â ðàçäåë