art.1SDA053442R1 - T2H 160 TMD100-1000 3p F F 50òÔìòÖÑC (C.BREAKER TMAX T2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 100-1000 A 50òÔìòÖÑC) | Quad Industry GmbH

Àðòèêóë: 1SDA053442R1
Íàèìåíîâàíèå: T2H 160 TMD100-1000 3p F F 50òÔìòÖÑC (C.BREAKER TMAX T2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 100-1000 A 50òÔìòÖÑC)
Ïðîèçâîäèòåëü: ABB


T2H 160 TMD100-1000 3p F F 50òÔìòÖÑC

General Information

  • Extended Product Type:
    T2H 160 TMD100-1000 3p F F 50òÔìòÖÑC
  • Product ID:
    1SDA053442R1
  • EAN:
    8015644543631
  • Catalog Description:
    T2H 160 TMD100-1000 3p F F 50òÔìòÖÑC
  • Long Description:
    C.BREAKER TMAX T2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 100-1000 A 50òÔìòÖÑC

Ordering

  • EAN:
    8015644543631
  • Customs Tariff Number:
    85362090

Additional Information

  • Electrical Durability:
    8000 cycle
    120 cycles per hour
  • Mechanical Durability:
    25000 cycle
    240 cycles per hour
  • Number of Poles:
    3
  • Power Loss:
    at Rated Operating Conditions per Pole 8,5 W
  • Product Main Type:
    SACE Tmax T
  • Product Name:
    Automatic Circuit Breaker
  • Product Type:
    CB
  • Rated Current (In):
    100 A
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Rated Insulation Voltage (Ui):
    800 V
  • Rated Operational Voltage:
    690 V AC
    500 V DC
  • Rated Service Short-Circuit Breaking Capacity (Ics):
    (220 V AC) 100 kA
    (230 V AC) 100 kA
    (380 V AC) 70 kA
    (400 V AC) 70 kA
    (415 V AC) 70 kA
    (440 V AC) 55 kA
    (500 V AC) 36 kA
    (690 V AC) 8 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (220 V AC) 10 kA
    (230 V AC) 10 kA
    (380 V AC) 70 kA
    (400 V AC) 70 kA
    (415 V AC) 70 kA
    (440 V AC) 55 kA
    (500 V AC) 36 kA
    (690 V AC) 8 kA
    (250 V DC) 2 Poles in Series 70 kA
    (250 V DC) 3 Poles in Series 85 kA
    (500 V DC) 3 Poles in Series 70 kA
  • Rated Uninterrupted Current (Iu):
    160 A
  • Release Type:
    TM
  • Standards:
    IEC 60947
  • Sub-type:
    T2
  • Terminal Connection Type:
    Fixed Circuit-Breakers
    Front
  • Test Voltage Max (Utest):
    3000 V
  • Version:
    F

Certificates and Declarations (Document Number)





Image 0 alt text

Categories

  • Products >> Low Voltage Products and Systems >> Circuit Breakers >> Moulded Case Circuit Breakers >> Tmax T


Íàçàä â ðàçäåë