Long Description:
The MS325-6.3-HKF11 manual motor starter is a 54 mm width devices with a rated operational current of Ie = 6.3 A and a pre-assembled front mounted auxiliary contact HKF1-11. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 VAC and the trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.
Spare Part Supplier Information - DEAPR858
Product Availability Class:
Ordering
Replacement Product ID (NEW):
Container Information
Package Level 1 Gross Weight:
Dimensions
Technical
Rated Service Short-Circuit Breaking Capacity (Ics):
(230V AC) 100 kA
(400V AC) 100 kA
(440V AC) 100 kA
(500V AC) 60 kA
(690V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230V AC) 100 kA
(400V AC) 100 kA
(440V AC) 100 kA
(500V AC) 60 kA
(690V AC) 10 kA
Rated Instantaneous Short-Circuit Current Setting (Ii):
Rated Operational Power AC-3 (Pe):
Rated Operational Voltage (Ue):
Main Circuit 690 V AC
Main Circuit 440 V DC
Rated Operational Current (Ie):
Rated Operational Current AC-3 (Ie):
Rated Impulse Withstand Voltage (Uimp):
Rated Insulation Voltage (Ui):
Number of Auxiliary Contacts NC:
Number of Auxiliary Contacts NO:
Conventional Free-air Thermal Current (Ith):
Connecting Capacity-Main Circuit:
Rigid 1/2x 1 ... 6 mm?
Flexible with Ferrule 1/2x 0.75 ... 4 mm?
Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm?
Flexible 1/2x 1 ... 6 mm?
Recommended Screw Driver:
Contact Position Indication:
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards:
IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL508, CSA 22.2 No. 14
Environmental
Ambient Air Temperature:
Operation -25 …. +70 °C
Operation Compensated -25 ... +50 °C
Storage -50 …+80 °C
Around the Enclosure 0 ... +40 °C
Ambient Air Temperature Compensation:
Maximum Operating Altitude Permissible:
Resistance to Shock acc. to IEC 60068-2-27:
Resistance to Vibrations acc. to IEC 60068-2-6:
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical UL/CSA
Maximum Operating Voltage UL/CSA:
Connecting Capacity-Main Circuit UL/CSA:
Stranded 1/2x 14 ... 8 AWG
Flexible 1/2x 14 ... 8 AWG
Tightening Torques UL/CSA:
Main Circuit 14 in·lb
Auxiliary Circuit 7 in·lb
Certificates and Declarations (Document Number)
Declaration of Conformity - CE:
Environmental Information: