art.1SFC132303F0001_720.jpg, 1SFC132184F0002_720.jpg, 1SFC132218F0001_720.jpg, 1SFC132186F0001_720.jpg, 1SFC132350F0001_720.jpg, 1SFC132224F0001_720.jpg - SOFTSTARTER | 1SFA893010R1002 | PSS142/245-690L | Quad Industry GmbH

Артикул: 1SFC132303F0001_720.jpg, 1SFC132184F0002_720.jpg, 1SFC132218F0001_720.jpg, 1SFC132186F0001_720.jpg, 1SFC132350F0001_720.jpg, 1SFC132224F0001_720.jpg
Наименование: SOFTSTARTER | 1SFA893010R1002 | PSS142/245-690L
Производитель: ABB
Картинки описания: 1SFA893010R1002


General Information
Extended Product Type:
PSS142/245-690L
Product ID:
1SFA893010R1002
EAN:
7320500215692
Catalog Description:
SOFTSTARTER
Long Description:
Softstarter PSS142/245-690L for max 690V main voltage and 220 - 240 V 50/60Hz Control Supply voltage having a NO fault contact
 
Ordering
EAN:
7320500215692
Minimum Order Quantity:
1 piece
Country of Origin:
Sweden (SE)
Customs Tariff Number:
85371099
Dimensions
Product Net Width:
181.000 mm
Product Net Height:
340.000 mm
Product Net Depth:
265.000 mm
Product Net Weight:
10.400 kg
Container Information
Package Level 1 Width:
235 mm
Package Level 1 Length:
450 mm
Package Level 1 Height:
315 mm
Package Level 1 Gross Weight:
11.6 kg
Package Level 1 Units:
1 piece
Package Level 2 Units:
1 piece
Technical
Rated Operational Voltage (Ue):
Main Circuit 400 … 690 V AC
Rated Control Supply Voltage (Us):
220 ... 240 V AC
Rated Control Circuit Voltage (Uc):
DC Operation 24 V
Rated Frequency (fr):
Main Circuit 50/60 Hz
Control Supply 50/60 Hz
Rated Operational Power - In-Line Connection (Pe):
at 400V 75 kW
at 500V 90 kW
at 690V 132 kW
Rated Operational Current - In-Line Connection (Ie):
142 A
Rated Operational Power - Inside Delta Connection:
at 400V 132 kW
at 500V 160 kW
at 690V 220 kW
Rated Operational Current - Inside Delta Connection:
245 A
Service Factor Percentage:
115 %
Overload Protection:
Recommended TA200DU 66 … 142
Integrated Electronic Overload:
No
Adjustable Rated Motor Current Ie:
No %
Starting Capacity at Maximum Rated Current Ie:
4xIe for 10s
Ramp Time:
During Start 1 ... 30 second(s)
During Stop 0 ... 30 second(s)
Initial Voltage During Start:
30 … 70 %
Step Down Voltage Special Ramp:
No %
Current Limit Function:
1.5 … 4 xIe if current transformer is connected
Switch for Inside Delta Connection:
Yes
Run Signal Relay:
No
By-pass Signal Relay:
Yes
Fault Signal Relay:
Yes, NO contact
Overload Signal Relay:
No
Signal indication completed start ramp (LED):
Green
Signal indication ready to start/standby ON (LED):
Green
Signal indication running R (LED):
Green
Signal indication fault (LED):
Red
Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time:
30
Communication:
No
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type:
Main Circuit: Bars
Connecting Capacity-Main Circuit:
Hole Diameter 8.5 mm
Width and Thickness 17.5x5 mm
Connecting Capacity-Control Circuit:
Rigid 2.5 mm?
Connecting Capacity-Supply Circuit:
Rigid 2.5 mm?
Tightening Torques:
Main Circuit 18 N·m
Supply Circuit 0.5 N·m
Control Circuit 0.5 N·m
Product Main Type:
PSS142/245
Certificates and Declarations (Document Number)
Declaration of Conformity - CE:
Environmental Information:
RoHS Information:
Environmental
Ambient Air Temperature:
Operation -25 … +60 °C
Storage -40 … +70 °C
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Classifications
UNSPSC:
39121521

PSS142/245-690L