art.T2_720.jpg, 1SDC210190F0004.jpg, AP3106_Group_Tmax_PV_3-4_1_L2_720.jpg, AP3106_Group_Tmax_front_1_L2_720.jpg - 3 poles | 1SDA053151R1 | Quad Industry GmbH

Артикул: T2_720.jpg, 1SDC210190F0004.jpg, AP3106_Group_Tmax_PV_3-4_1_L2_720.jpg, AP3106_Group_Tmax_front_1_L2_720.jpg
Наименование: 3 poles | 1SDA053151R1
Производитель: ABB
Картинки описания: 1SDA053151R1


General Information
Product ID:
1SDA053151R1
EAN:
8015644540081
Catalog Description:
T2L 160 MF8,5 Im=110A 3P F F
Long Description:
Automatic moulded case circuit-breaker for motor protection, SACE Tmax T2, Icu 415 V AC = 85kA, Size Iu = 160A , Magnetic trip unit with fixed threshold, In = 8.5A, Im = 110A, 3 poles, Version = Fixed, connection terminal = Front terminal
 
Ordering
EAN:
8015644540081
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362090
Dimensions
Product Net Width:
90 mm
Product Net Height:
130 mm
Product Net Depth:
70 mm
Product Net Weight:
1.1 kg
Container Information
Package Level 1 Units:
1 piece
Package Level 1 Width:
128 mm
Package Level 1 Height:
135 mm
Package Level 1 Length:
143 mm
Package Level 1 Gross Weight:
1.2 kg
Package Level 1 EAN:
8015644540081
Environmental
RoHS Status:
Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2006-07-01
Additional Information
Electrical Durability:
25000
IIT Publishing Status:
Level 0 - Information enabled
Number of Poles:
3
Power Loss:
Per Pole 2.7 W
Product Main Type:
SACE Tmax
Product Name:
T2
Rated Current (In):
160 A
Rated Operational Voltage (Ue):
690 V AC
Release Type:
M13
Standards:
IEC 60947
Suitable For:
T2
Suitable for Product Class:
Moulded Case Circuit Breakers
Terminal Connection Type:
Fixed Circuit-Breakers
Test Voltage at Industrial Frequency for 1 Minute:
3000 V
Version:
Fixed
Certificates and Declarations (Document Number)
Declaration of Conformity - CE:
Environmental Information:
RoHS Information:
Classifications
Object Classification Code:
Q
UNSPSC:
39121100