art. - Miniature Circuit Breaker - S200M - Number of Poles 2 - Tripping characteristic C - Rated Current 1.60 A | 2CDS272001R0974 | S202M-C1,6 | Quad Industry GmbH

Наименование: Miniature Circuit Breaker - S200M - Number of Poles 2 - Tripping characteristic C - Rated Current 1.60 A | 2CDS272001R0974 | S202M-C1,6
Производитель: ABB
Картинки описания: 2CDS272001R0974


General Information
Extended Product Type:
S202M-C1,6
Product ID:
2CDS272001R0974
EAN:
4016779550215
Catalog Description:
Miniature Circuit Breaker - S200M - Number of Poles 2 - Tripping characteristic C
Long Description:
System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
 
Ordering
EAN:
4016779550215
Minimum Order Quantity:
1 piece
Country of Origin:
Germany (DE)
Container Information
Package Level 1 Units:
5 piece
Package Level 1 Width:
92.0 mm
Package Level 1 Length:
183.0 mm
Package Level 1 Height:
80.0 mm
Package Level 1 Gross Weight:
1.300 kg
Package Level 1 EAN:
4016779605830
Dimensions
Product Net Width:
35.0 mm
Product Net Depth:
69.0 mm
Product Net Height:
88.0 mm
Product Net Weight:
0.250 kg
Technical
Standards:
IEC/EN 60898-1
IEC/EN 60947-2
Number of Poles:
2
Tripping Characteristic:
C
Rated Current (In):
1.60 A
Rated Operational Voltage (Ue):
400 V AC
Rated Insulation Voltage (Ui):
Phase to Ground 250 V AC
Phase to Phase 500 V AC
Operational Voltage:
Maximum 440 V AC
Maximum 125 V DC
Minimum 12 V AC
Minimum 12 V DC
Rated Frequency (fr):
50 / 60 Hz
Rated Short-Circuit Capacity ( Icn
):
10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
15 kA
Rated Service Short-Circuit Breaking Capacity (Ics):
11.2 kA
Energy Limiting Class:
3
Overvoltage Category:
III
Pollution Degree:
2
Rated Impulse Withstand Voltage (Uimp):
4 kV
(6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage:
50/60 Hz, 1 min.: 2 kV
Housing Material:
Insulation group I, RAL 7035
Actuator Type:
Insulation group II, black, sealable
Actuator Marking:
I / O
Contact Position Indication:
ON / OFF
Degree of Protection:
IP20
Remarks:
IP40 in enclosure with cover
Electrical Endurance (Nelec):
20000 cycle
Mechanical Endurance (Nendu):
20000 cycle
Terminal Type:
Screw Terminals
Screw Terminal Type:
Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity:
Busbar 10 / 10 mm??
Rigid 0.75...25 mm??
Stranded 0.75...25 mm??
Flexible 0.75...16 mm??
Flexible with Ferrule 0.75...16 mm??
Tightening Torques:
2.8 N??m
Recommended Screw Driver:
Pozidriv 2
Mounting on DIN Rail:
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting Position:
Any
Technical UL/CSA
Tightening Torques UL/CSA:
25 in??lb
Environmental
Ambient Air Temperature:
Operation -25 тАж +55 ??C
Storage -40 ... +70 ??C
Reference Temperature for Tripping Characteristics:
30 ??C
Resistance to Shock acc. to IEC 60068-2-27:
30g, 3 shocks, 11 ms
Resistance to Vibrations acc. to IEC 60068-2-6:
5g, 20 cycles at 5...150...5 Hz with load 0.8 In
Environmental Conditions:
28 cycles
with 55 ??C / 90-96%
and 25 ??C / 95-100%
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Certificates and Declarations (Document Number)
Declaration of Conformity - CE:
Environmental Information:
RoHS Information:
Classifications
E-nummer:
E2101219
ETIM 4.0:
EC000042 - Miniature circuit breaker (MCB)
ETIM 5.0:
EC000042 - Miniature circuit breaker (MCB)