art. - Miniature Circuit Breakers MCBs - S290 - Number of Poles 3 - Tripping characteristic D - Rated Current 80.00 A | GHS2932001R0801 | S293-D80 | Quad Industry GmbH

Наименование: Miniature Circuit Breakers MCBs - S290 - Number of Poles 3 - Tripping characteristic D - Rated Current 80.00 A | GHS2932001R0801 | S293-D80
Производитель: ABB
Картинки описания: GHS2932001R0801


General Information
Extended Product Type:
S293-D80
Product ID:
GHS2932001R0801
EAN:
4016779570695
Catalog Description:
Miniature Circuit Breakers MCBs - S290 - Number of Poles 3 - Tripping characteristic D
Long Description:
S290 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,K), configurations (1P,2P,3P,4P), breaking capacities (up to 20 kA at 230/400 V AC) and rated currents (up to 125A). All MCBs of the product range S290 comply with IEC/EN 60898-1, IEC/EN 60947-2 and UL1077, allowing the use for residential, commercial and industrial applications.
 
Ordering
EAN:
4016779570695
Minimum Order Quantity:
1 piece
Country of Origin:
Greece (GR)
Container Information
Package Level 1 Units:
2 piece
Package Level 1 Width:
92.0 mm
Package Level 1 Length:
166.0 mm
Package Level 1 Height:
82.0 mm
Package Level 1 Gross Weight:
1.610 kg
Dimensions
Product Net Width:
78.8 mm
Product Net Depth:
70.0 mm
Product Net Height:
90.0 mm
Product Net Weight:
0.790 kg
Technical
Standards:
IEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Number of Poles:
3
Tripping Characteristic:
D
Rated Current (In):
80.00 A
Rated Operational Voltage (Ue):
400 V AC
Rated Insulation Voltage (Ui):
Phase to Ground 250 V AC
Phase to Phase 500 V AC
Operational Voltage:
Maximum 253 / 440 V AC
Maximum 125 V DC
Minimum 24 V AC / 24 V DC
Rated Frequency (fr):
50 / 60 Hz
Rated Short-Circuit Capacity ( Icn
):
10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
20 kA
Rated Service Short-Circuit Breaking Capacity (Ics):
10 kA (AC) kA
Overvoltage Category:
III
Pollution Degree:
3
Rated Impulse Withstand Voltage (Uimp):
4 kV
(6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage:
50/60 Hz, 1 min.: 2 kV
Actuator Type:
Insulation group II, black, sealable
Actuator Marking:
I / O
Contact Position Indication:
ON / OFF
Degree of Protection:
IP20
Remarks:
IP40 in enclosure with cover
Electrical Endurance (Nelec):
10000 cycle
Mechanical Endurance (Nendu):
20000 cycle
Terminal Type:
Screw Terminals
Screw Terminal Type:
Cable Clamp
Connecting Capacity:
Conductor 50 / 50 mm??
Tightening Torques:
2.5 ... 3.5 N??m
Recommended Screw Driver:
Pozidriv 2
Mounting on DIN Rail:
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting Position:
Any
Technical UL/CSA
Maximum Operating Voltage UL/CSA:
480 / 277 V AC
Connecting Capacity UL/CSA:
Busbar 14 -2 AWG
Tightening Torques UL/CSA:
22 ... 31 in??lb
Interrupting Rating acc. to UL1077:
5.0 kA
Environmental
Ambient Air Temperature:
Operation -25 ... +45 ??C
Storage -40 ... +70 ??C
Reference Temperature for Tripping Characteristics:
30 ??C
Resistance to Shock acc. to IEC 60068-2-27:
15g, 1 shock, 11 ms
Resistance to Vibrations acc. to IEC 60068-2-6:
5g, at 25...150 Hz, 6g at 35Hz with load 0.8 In
Environmental Conditions:
28 cycles
with 55 ??C / 90-96%
and 25 ??C / 95-100%
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Certificates and Declarations (Document Number)
Declaration of Conformity - CE:
Environmental Information:
RoHS Information:
Classifications
ETIM 4.0:
EC000042 - Miniature circuit breaker (MCB)
ETIM 5.0:
EC000042 - Miniature circuit breaker (MCB)


Назад в раздел