art.1SFL657001R7022 - AF1350-30-22 100-250V 50/60Hz / 100-250V DC Contactor (A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/D | Quad Industry GmbH

Àðòèêóë: 1SFL657001R7022
Íàèìåíîâàíèå: AF1350-30-22 100-250V 50/60Hz / 100-250V DC Contactor (A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC)
Ïðîèçâîäèòåëü: ABB


AF1350-30-22 100-250V 50/60Hz / 100-250V DC

General Information

  • Extended Product Type:
    AF1350-30-22 100-250V 50/60Hz / 100-250V DC
  • Product ID:
    1SFL657001R7022
  • EAN:
    7320500250150
  • Catalog Description:
    AF1350-30-22 100-250V 50/60Hz / 100-250V DC Contactor
  • Long Description:
    A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC

Ordering

  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Popular Downloads

Dimensions

  • Product Net Width:
    438.0 mm
  • Product Net Depth:
    244.0 mm
  • Product Net Height:
    392.0 mm
  • Product Net Weight:
    33.000 kg

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    2
  • Number of Auxiliary Contacts NC:
    2
  • Rated Operational Voltage:
    Main Circuit 1000 V
  • Rated Frequency (f):
    Main Circuit 50/60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 1350 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 55 °C 1150 A
    (690 V) 40 °C 1350 A
    (1000 V) 40 °C 1350 A
    (1000 V) 55 °C 1150 A
    (690 V) 70 °C 1000 A
    (1000 V) 70 °C 1000 A
  • Rated Operational Current AC-3 (Ie):
    (690 V) 55 °C 800 A
    (500 V) 55 °C 800 A
    (440 V) 55 °C 860 A
    (415 V) 55 °C 860 A
    (380 / 400 V) 55 °C 860 A
    (220 / 230 / 240 V) 55 °C 860 A
  • Rated Operational Power AC-3 (Pe):
    (220 / 230 / 240 V) 257 kW
    (380 / 400 V) 475 kW
    (415 V) 500 kW
    (440 V) 560 kW
    (500 V) 560 kW
    (690 V) 800 kW
    (1000 V) 560 kW
  • Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
    10 x Ie AC-3
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 8000 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1600 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 6000 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 10000 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 4500 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 10000 A
  • Maximum Electrical Switching Frequency:
    AC-3 60 cycles per hour
    AC-1 60 cycles per hour
    AC-2 / AC-4 60 cycles per hour
  • Rated Operational Current DC-1 (Ie):
    (850 V) 3 Poles in Series, 40 °C 1350 A
    (600 V) 3 Poles in Series, 40 °C 1350 A
    (220 V) 3 Poles in Series, 40 °C 1350 A
  • Rated Operational Current DC-3 (Ie):
    (850 V) 3 Poles in Series, 40 °C 1350 A
    (600 V) 3 Poles in Series, 40 °C 1350 A
    (220 V) 3 Poles in Series, 40 °C 1350 A
  • Rated Operational Current DC-5 (Ie):
    (850 V) 3 Poles in Series, 40 °C 1350 A
    (600 V) 3 Poles in Series, 40 °C 1350 A
    (220 V) 3 Poles in Series, 40 °C 1350 A
  • Rated Insulation Voltage (Ui):
    acc. to UL/CSA 600 V
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
  • Rated Impulse Withstand Voltage (Uimp):
    Main Circuit 8 kV
  • Mechanical Durability:
    0.5 million
  • Maximum Mechanical Switching Frequency:
    300 cycles per hour
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
  • Rated Control Circuit Voltage (Uc):
    60 Hz 100 … 250 V
    50 Hz 100 … 250 V
    DC Operation 100 … 250 V
  • Coil Consumption:
    Pull-in at Max. Rated Control Circuit Voltage 60 Hz 2450 V·A
    Holding at Max. Rated Control Circuit Voltage DC 20.5 V·A
    Holding at Max. Rated Control Circuit Voltage 50 Hz 48 V·A
    Pull-in at Max. Rated Control Circuit Voltage DC 2290 V·A
    Pull-in at Max. Rated Control Circuit Voltage 50 Hz 2450 V·A
    Holding at Max. Rated Control Circuit Voltage 60 Hz 48 V·A
  • Operate Time:
    Between Coil Energization and NO Contact Closing 50 ... 80 ms
    Between Coil De-energization and NO Contact Opening 35 ... 55 ms
    Between Coil De-energization and NC Contact Closing 35 ... 55 ms
    Between Coil Energization and NC Contact Opening 50 ... 80 ms
  • Connecting Capacity Main Circuit:
    Bar 100 mm
  • Connecting Capacity Auxiliary Circuit:
    Solid 2x1…4 mm²
    Flexible with Insulated Ferrule 2x0.75…2.5 mm²
    Stranded 1x1…4 mm²
    Flexible 1x0.75…2.5 mm²
    Flexible with Ferrule 1x0.75…2.5 mm²
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
  • Terminal Type:
    Main Circuit: Bars

Environmental

  • Ambient Air Temperature:
    Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
    Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
    Close to Contactor for Storage -40…+70 °C
  • Maximum Operating Altitude Permissible:
    3000 m
  • RoHS Status:
    No declaration needed

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:
    Main Circuit 600 V
  • General Use Rating UL/CSA:
    (600 V AC) 1350 A
  • Horsepower Rating UL/CSA:
    (440 ... 480 V AC) Three Phase 800 Hp
    (550 ... 600 V AC) Three Phase 1000 Hp
    (220 ... 240 V AC) Three Phase 400 Hp

Certificates and Declarations (Document Number)

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    250 mm
  • Package Level 1 Length:
    440 mm
  • Package Level 1 Height:
    430 mm
  • Package Level 1 Gross Weight:
    38 kg
  • Package Level 1 EAN:
    7320500250150
  • Package Level 2 Units:
    1

Classifications

  • Object Classification Code:
    Q
  • ETIM 4:
    EC000066 - Magnet contactor, AC-switching
  • ETIM 5:
    EC000066 - Magnet contactor, AC-switching
  • ETIM 6:
    EC000066 - Power contactor, AC switching
  • UNSPSC:
    39121529

Where Used (as a spare part for "Products")

Identifier Qty Unit Of Measure Description
ACS 5000 Water Cooled 1 piece No Description Available
ACS 6000 piece 1 No Description Available



Categories

  • Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
  • Parts & Services » Drives » Medium voltage AC drives » Special purpose drives » ACS5000
  • Parts & Services » Drives » Medium voltage AC drives » Special purpose drives » ACS6000


Íàçàä â ðàçäåë