art.1SFL451001R8000 - A110-30-00 220-230V 50Hz / 230-240V 60Hz Contactor (A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24?âòÂì?æ.690 A | Quad Industry GmbH
Àðòèêóë: 1SFL451001R8000
Íàèìåíîâàíèå: A110-30-00 220-230V 50Hz / 230-240V 60Hz Contactor (A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24?âòÂì?æ.690 AC, 50 and 60 Hz)
Ïðîèçâîäèòåëü: ABB
Êàðòèíêè îïèñàíèÿ: 1SFL451001R8000.jpg, 1SFC101044F0202_720.jpg, 1SFC101043F0202_720.jpg, acrosstheline.jpg, CP_Block_Contactors.jpg, 1SBC101292F0010_720.jpg
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24?âòÂì?æ.690 AC, 50 and 60 Hz
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
10 x Ie AC-3
Short-Circuit Protective Devices:
gG Type Fuses 200 A
Rated Short-time Withstand Current (Icw):
at 40 ??C Ambient Temp, in Free Air, from a Cold State 15 min 175 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 30 s 500 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 10 s 800 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 s 1320 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 min 350 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A
Maximum Electrical Switching Frequency:
AC-3 300 cycles per hour AC-1 300 cycles per hour AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie):
(110 V) 2 Poles in Series, 40 ??C 160 A (220 V) 3 Poles in Series, 40 ??C 160 A
Rated Operational Current DC-3 (Ie):
(110 V) 2 Poles in Series, 40 ??C 160 A (220 V) 3 Poles in Series, 40 ??C 160 A
Rated Operational Current DC-5 (Ie):
(110 V) 2 Poles in Series, 40 ??C 160 A (220 V) 3 Poles in Series, 40 ??C 160 A
Rated Insulation Voltage (Ui):
acc. to UL/CSA 600 V acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage (Uimp):
Main Circuit 8 kV
Mechanical Durability:
10 million
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at ?? òÉä 70 ??C) ??C
Rated Control Circuit Voltage (Uc):
60 Hz 230 òÀæ 240 V 50 Hz 220 òÀæ 230 V
Coil Consumption:
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 450 V??A Holding at Max. Rated Control Circuit Voltage 50 Hz 22 V??A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V??A Holding at Max. Rated Control Circuit Voltage 60 Hz 26 V??A
Operate Time:
Between Coil Energization and NO Contact Closing 10 ... 25 ms Between Coil De-energization and NC Contact Closing 7 ... 15 ms
Connecting Capacity Main Circuit:
Flexible with Cable End 1x10òÀæ70 mm?? Bar 30 mm?? Rigid 2x6òÀæ65 mm??
Connecting Capacity Auxiliary Circuit:
Solid 2x1òÀæ4 mm?? Flexible with Insulated Ferrule 2x0.75òÀæ2.5 mm?? Stranded 2x1òÀæ4 mm?? Flexible 2x0.75òÀæ2.5 mm?? Flexible with Ferrule 2x0.75òÀæ2.5 mm??
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Connecting terminals (delivered in open position) Main poles:
M8 hexagon socket screw with single connector
Terminal Type:
Cable Clamp
Environmental
Ambient Air Temperature:
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25òÀæ+50 ??C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40òÀæ+70 ??C Close to Contactor for Storage -60òÀæ+80 ??C
Maximum Operating Altitude Permissible:
3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 10 g Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 15 g Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 g Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 g
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical UL/CSA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V
General Use Rating UL/CSA:
(600 V AC) 140 A
Horsepower Rating UL/CSA:
(208 V AC) Three Phase 30 Hp (440 ... 480 V AC) Three Phase 75 Hp (550 ... 600 V AC) Three Phase 100 Hp (220 ... 240 V AC) Three Phase 40 Hp (200 V AC) Three Phase 30 Hp