art.1SFL497001R7022 - AF185-30-22 100-250V 50/60Hz / 100-250V DC Contactor (A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC | Quad Industry GmbH
Àðòèêóë: 1SFL497001R7022
Íàèìåíîâàíèå: AF185-30-22 100-250V 50/60Hz / 100-250V DC Contactor (A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC)
Ïðîèçâîäèòåëü: ABB
AF185-30-22 100-250V 50/60Hz / 100-250V DC
General Information
Extended Product Type:
AF185-30-22 100-250V 50/60Hz / 100-250V DC
Product ID:
1SFL497001R7022
EAN:
7320500222713
Catalog Description:
AF185-30-22 100-250V 50/60Hz / 100-250V DC Contactor
Long Description:
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
10 x Ie AC-3
Short-Circuit Protective Devices:
gG Type Fuses 355 A
Rated Short-time Withstand Current (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 320 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 800 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1600 A
Maximum Electrical Switching Frequency:
AC-3 300 cycles per hour AC-1 300 cycles per hour AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie):
(110 V) 2 Poles in Series, 40 °C 275 A (220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-3 (Ie):
(110 V) 2 Poles in Series, 40 °C 275 A (220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-5 (Ie):
(110 V) 2 Poles in Series, 40 °C 275 A (220 V) 3 Poles in Series, 40 °C 275 A
Rated Insulation Voltage (Ui):
acc. to UL/CSA 600 V acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage (Uimp):
Main Circuit 8 kV
Mechanical Durability:
5 million
Maximum Mechanical Switching Frequency:
300 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc):
60 Hz 100 … 250 V 50 Hz 100 … 250 V DC Operation 100 … 250 V
Coil Consumption:
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 430 V·A Holding at Max. Rated Control Circuit Voltage DC 2 W Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A Pull-in at Max. Rated Control Circuit Voltage DC 500 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 430 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A
Operate Time:
Between Coil Energization and NO Contact Closing 50 ... 90 ms Between Coil De-energization and NO Contact Opening 43 ... 53 ms Between Coil De-energization and NC Contact Closing 40 .... 50 ms Between Coil Energization and NC Contact Opening 45 ... 85 ms
Connecting Capacity Main Circuit:
Rigid Al-Cable 25…150 mm² Bar 24 mm Rigid Cu-Cable 6…185 mm²
Connecting Capacity Auxiliary Circuit:
Solid 2x1…4 mm² Flexible with Insulated Ferrule 2x0.75…2.5 mm² Stranded 2x1…4 mm² Flexible 1x0.75…2.5 mm² Flexible with Ferrule 2x0.75…2.5 mm²
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type:
Main Circuit: Bars
Environmental
Ambient Air Temperature:
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C Close to Contactor for Storage -40…+70 °C
Maximum Operating Altitude Permissible:
3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Shock Direction: A 5 g Shock Direction: C2 5 g Shock Direction: B2 5 g Shock Direction: C1 5 g Shock Direction: B1 5 g
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical UL/CSA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V
General Use Rating UL/CSA:
(600 V AC) 250 A
Horsepower Rating UL/CSA:
(208 V AC) Three Phase 50 Hp (440 ... 480 V AC) Three Phase 125 Hp (550 ... 600 V AC) Three Phase 150 Hp (220 ... 240 V AC) Three Phase 60 Hp (200 V AC) Three Phase 50 Hp