art.1SBL183201R8300 - AL16-40-00 48V DC Contactor (AL16 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also b | Quad Industry GmbH
Àðòèêóë: 1SBL183201R8300
Íàèìåíîâàíèå: AL16-40-00 48V DC Contactor (AL16 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also be used for many other applications such lighting... The AL... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: DC operated with solid core magnet circuit. The polarity on the coil terminals (A1+ and A2-) must be respected - Accessories: a wide range of accessories is available. AL... contactors are fitted with low consumption DC coils and are suitable for a direct control by PLC outputs.)
Ïðîèçâîäèòåëü: ABB
AL16-40-00 48V DC
General Information
Extended Product Type:
AL16-40-00 48V DC
Product ID:
1SBL183201R8300
EAN:
3471522278838
Catalog Description:
AL16-40-00 48V DC Contactor
Long Description:
AL16 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also be used for many other applications such lighting... The AL... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: DC operated with solid core magnet circuit. The polarity on the coil terminals (A1+ and A2-) must be respected - Accessories: a wide range of accessories is available. AL... contactors are fitted with low consumption DC coils and are suitable for a direct control by PLC outputs.
acc. to IEC 60947-4-1, Open Contactors q = 40 ??C 30 A
Rated Operational Current AC-1 (Ie):
(690 V) 40 ??C 30 A (690 V) 55 ??C 27 A (690 V) 70 ??C 23 A
Rated Operational Current AC-3 (Ie):
(220 / 230 / 240 V) 55 ??C 17 A (380 / 400 V) 55 ??C 17 A (415 V) 55 ??C 17 A (440 V) 55 ??C 16 A (500 V) 55 ??C 14 A (690 V) 55 ??C 10 A
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
10 x Ie AC-3
Short-Circuit Protective Devices:
gG Type Fuses 32 A
Rated Short-time Withstand Current (Icw):
at 40 ??C Ambient Temp, in Free Air, from a Cold State 10 s 140 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 15 min 30 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 min 60 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 s 300 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 100 A
Maximum Electrical Switching Frequency:
AC-1 600 cycles per hour AC-2 / AC-4 300 cycles per hour AC-3 1200 cycles per hour
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at ?? òÉä 55 ??C) ??C
Rated Control Circuit Voltage (Uc):
DC Operation 48 V
Coil Consumption:
Average Holding Value, from Warm State 3 W Average Pull-in Value, from Cold State 3 W
Operate Time:
Between Coil Energization and NO Contact Closing 50 ... 100 ms Between Coil De-energization and NO Contact Opening 10 ... 17 ms
Connecting Capacity Main Circuit:
Flexible with Cable End 0.75 ... 2.5 mm?? Rigid Cable 1 ... 4 mm??
Connecting Capacity Auxiliary Circuit:
Flexible with Cable End 0.75 ... 2.5 mm?? Rigid Cable 1 ... 4 mm??
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Connecting terminals (delivered in open position) Main poles:
M 3.5 (+,-) pozidriv 2 screw with cable clamp
Terminal Type:
Screw Terminals
Environmental
Ambient Air Temperature:
Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 ??C Near Contactor for Operation in Free Air (Uc) -40 ... +70 ??C Close to Contactor for Storage -60 ... +80 ??C
Climatic Withstand:
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible:
3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Closed, Shock Direction: A 20 g Open, Shock Direction: A 10 g Closed, Shock Direction: B1 15 g Open, Shock Direction: B1 5 g Shock Direction: B2 10 g Closed, Shock Direction: C1 20 g Open, Shock Direction: C1 8 g Closed, Shock Direction: C2 14 g Open, Shock Direction: C2 8 g
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment