art.1SAZ431301R1002 - TF140DU-110-V-1000 Thermal Overload Relay (TF140DU-110-V-1000 Thermal Overload Relay with ATEX) | Quad Industry GmbH

Артикул: 1SAZ431301R1002
Наименование: TF140DU-110-V-1000 Thermal Overload Relay (TF140DU-110-V-1000 Thermal Overload Relay with ATEX)
Производитель: ABB


TF140DU-110-V-1000

General Information

  • Extended Product Type:
    TF140DU-110-V-1000
  • Product ID:
    1SAZ431301R1002
  • EAN:
    4013614499524
  • Catalog Description:
    TF140DU-110-V-1000 Thermal Overload Relay
  • Long Description:
    TF140DU-110-V-1000 Thermal Overload Relay with ATEX

Ordering

  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Dimensions

  • Product Net Width:
    89 mm
  • Product Net Height:
    140 mm
  • Product Net Depth:
    126 mm
  • Product Net Weight:
    0.82 kg

Popular Downloads

Technical

  • Setting Range:
    80 ... 110 A
  • Rated Operational Voltage:
    Auxiliary Circuit 440 V DC
    Auxiliary Circuit 500 V AC
    Main Circuit 690 V AC
  • Rated Operational Current (Ie):
    110 A
  • Rated Operational Current AC-3 (Ie):
    110 A
  • Rated Frequency (f):
    Auxiliary Circuit 50 Hz
    Auxiliary Circuit 60 Hz
    Auxiliary Circuit DC
    Main Circuit 60 Hz
    Main Circuit 50 Hz
    Main Circuit DC
  • Rated Impulse Withstand Voltage (Uimp):
    Auxiliary Circuit 6 kV
    Main Circuit 8 kV
  • Rated Insulation Voltage (Ui):
    690 V
  • Number of Poles:
    3
  • Number of Auxiliary Contacts NC:
    1
  • Number of Auxiliary Contacts NO:
    1
  • Number of Protected Poles:
    3
  • Conventional Free-air Thermal Current (Ith):
    Auxiliary Circuit NC 10 A
    Auxiliary Circuit NO 6 A
  • Rated Operational Current AC-15 (Ie):
    (120 V) NC 3 A
    (120 V) NO 1.5 A
    (240 V) NC 3 A
    (240 V) NO 1.5 A
    (400 V) NC 1.9 A
    (400 V) NO 1 A
    (440 V) NC 1 A
    (440 V) NO 1 A
    (500 V) NC 1 A
    (500 V) NO 1 A
  • Rated Operational Current DC-13 (Ie):
    (125 V) NC 0.25 A
    (125 V) NO 0.25 A
    (24 V) NC 1.25 A
    (24 V) NO 1.25 A
    (250 V) NC 0.12 A
    (250 V) NO 0.04 A
    (60 V) NC 0.25 A
    (60 V) NO 0.25 A
  • Degree of Protection:
    Housing IP20
    Main Circuit Terminals IP10
  • Pollution Degree:
    3
  • Connecting Capacity Auxiliary Circuit:
    Flexible with Ferrule 1/2x 0.75 ... 2.5 mm??
    Flexible 1/2x 0.75 ... 2.5 mm??
    Rigid 1/2x 0.75 ... 4 mm??
  • Connecting Capacity Main Circuit:
    Flexible with Ferrule 1/2x 16 ... 70 mm??
    Flexible with Insulated Ferrule 1/2x 16 ... 70 mm??
    Flexible 1/2x 16 ... 70 mm??
    Rigid 1/2x 16 ... 70 mm??
  • Tightening Torque:
    Auxiliary Circuit 0.8 ... 1.2 N??m
    Main Circuit 8 ... 10 N??m
  • Wire Stripping Length:
    Auxiliary Circuit 9 mm
    Main Circuit 25 mm
  • Recommended Screw Driver:
    Auxiliary Circuit Pozidriv 2
    Main Circuit Hexagon 4
  • Suitable For:
    AF116
    AF140
  • Standards:
    IEC/EN 60947-1
    IEC/EN 60947-4-1
    IEC/EN 60947-5-1
    UL 60947-1
    UL 60947-4-1

Environmental

  • Ambient Air Temperature:
    Operation -25 ... +55 ??C
    Operation Compensated -25 ... +55 ??C
    Storage -40 ... +70 ??C
  • Ambient Air Temperature Compensation:
    Yes
  • Maximum Operating Altitude Permissible:
    2000 m
  • Resistance to Shock acc. to IEC 60068-2-27:
    11 ms Pulse 12g
  • RoHS Status:
    Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:
    Main Circuit 600 V AC
  • Ampere Rating UL/CSA:
    110 A
  • Contact Rating UL/CSA:
    (NC:) B600
    (NO:) C300
  • Connecting Capacity Main Circuit UL/CSA:
    Flexible 1/2x 6-2/0 AWG
    Stranded 1/2x 6-2/0 AWG
  • Connecting Capacity Auxiliary Circuit UL/CSA:
    Flexible 1/2x 18-14 AWG
    Stranded 1/2x 18-14 AWG
  • Tightening Torque UL/CSA:
    Auxiliary Circuit 12 in??lb

Certificates and Declarations (Document Number)

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    165 mm
  • Package Level 1 Height:
    133 mm
  • Package Level 1 Length:
    151 mm
  • Package Level 1 Gross Weight:
    0.945 kg
  • Package Level 2 Units:
    4 piece
  • Package Level 2 Width:
    280 mm
  • Package Level 2 Height:
    210 mm
  • Package Level 2 Length:
    395 mm
  • Package Level 2 Gross Weight:
    8.786 kg
  • Package Level 2 EAN:
    4013614503726

Classifications

  • ETIM 5:
    EC000106 - Thermal overload relay
  • ETIM 6:
    EC000106 - Thermal overload relay
  • eClass:
    7.0 27371501
  • UNSPSC:
    39121521




Image 0 alt text

Categories

  • Products >> Low Voltage Products and Systems >> Control Products >> Contactors >> Thermal Overload Relays


Назад в раздел