art.1SAZ321201R2005 - TA75DU-63M Thermal Overload Relays (TA75DU-63M (45.0-63.0A) thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The de | Quad Industry GmbH
Àðòèêóë: 1SAZ321201R2005
Íàèìåíîâàíèå: TA75DU-63M Thermal Overload Relays (TA75DU-63M (45.0-63.0A) thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10A. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP- and Test function and a trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.)
Ïðîèçâîäèòåëü: ABB
TA75DU-63M
General Information
Extended Product Type:
TA75DU-63M
Product ID:
1SAZ321201R2005
EAN:
4013614482663
Catalog Description:
TA75DU-63M Thermal Overload Relays
Long Description:
TA75DU-63M (45.0-63.0A) thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10A. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP- and Test function and a trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.
Auxiliary Circuit 440/500 V AC/DC Main Circuit 690 V AC
Rated Operational Current (Ie):
63 A
Rated Operational Current AC-3 (Ie):
63 A
Rated Frequency (f):
Auxiliary Circuit DC/50/60 Hz Main Circuit DC/50/60 Hz
Rated Impulse Withstand Voltage (Uimp):
Auxiliary Circuit 6 kV Main Circuit 6 kV
Rated Insulation Voltage (Ui):
690 V
Number of Poles:
3
Number of Auxiliary Contacts NC:
1
Number of Auxiliary Contacts NO:
1
Number of Protected Poles:
3
Conventional Free-air Thermal Current (Ith):
Auxiliary Circuit NC 5 A Auxiliary Circuit NO 5 A
Rated Operational Current AC-15 (Ie):
(120 V) NC 3.000 A (120 V) NO 1.500 A (240 V) NC 3.000 A (240 V) NO 1.500 A (400 V) NC 1.900 A (400 V) NO 1.000 A (440 V) NC 1.000 A (440 V) NO 1.000 A (500 V) NC 1.000 A (500 V) NO 1.000 A
Rated Operational Current DC-13 (Ie):
(125 V) NC 0.250 A (125 V) NO 0.250 A (24 V) NC 1.250 A (24 V) NO 1.250 A (250 V) NC 0.120 A (250 V) NO 0.040 A (60 V) NC 0.250 A (60 V) NO 0.250 A